Installation Instructions

Valve should be installed and adjusted by a licensed contractor in accordance with 

local codes and ordinances. Further, this valve should be installed in a location where 

it is accessible for cleaning, service or adjustment.

1.  

Close both the hot and cold water shutoff valves upstream nearest to the intended 

installation.

2. Bleed the remaining water from the system.
3.  Connect the water supply to valve as shown in Figure 1, 2 or 3 depending on appli-

cation. Supply piping must be flushed clean before making connections to the valve.

4.  Valve can be installed in any position. Note: the inlet hot supply is to be connected 

to the “H” side of the valve, the cold supply side to the “C” side and the mixed water 

outlet to the “M” side.

5.  Make sure union nuts are placed over tailpieces prior to soldering or threading to pipe.
6.  For valves with Quick-Connect tailpieces refer to "Quick-Connect Installation" 

instructions below

Note:

 

To prevent damage to valve from excessive heat during  

soldering, remove unions and gaskets from valve body prior  

to soldering.
7.  After soldering, flush piping and install valve using filter washer 

on hot and cold water inlet and fiber washer on the mixed  

water outlet.

8.  Start-up: Open cold water supply, then hot water supply.  

Inspect for leaks.

9.  Adjust temperature to desired setting (see Temperature  

Adjustment Section). Watts recommends a maximum  

temperature of 110°F (43°C) for shower and bathing fixtures.

Series MMV and LFMMV

Thermostatic Tempering Valves

Sizes: 

1

2

", 

3

4

", 1" (15, 20, 25mm)

IS-MMV-M1

LFMMV-UT-M1

MMV-QC-M1

Quick-Connect Installation

1.  Mark pipe as shown.  

This is pipe insertion depth.

2. Clean pipe end.

1. Remove collet clip.

2. Depress collet.

3. Pull tubing from tailpiece.

3.  If using PEX tubing, insert pipe 

stiffener (provided) into end of pipe.

4.  Push tubing into tailpiece up to mark.

5. Insert collet clip.

  To Connect

  To Disconnect

PEX tubing only

Pipe Stiffener

Tail Piece

Mark

Collet clip

Collet depressed

1

1

/

2

 in. (38.1mm)

1

3

/

4

 in. (44.45mm)

1

7

/

8

 in. (47.63mm)

1

/

2

 in.Pipe (12.7mm)

3

/

4

 in.Pipe (19.05mm)

1 in.Pipe (25.4mm)

Figure 1 – Typical ASSE 1069 Application

Typical MMV-M1 and LFMMV-M1 Applications

Cold

Hot

MMV-M1 or 

LFMMV-M1

Mixed

Triple Listed! 

ASSE 1017,  

ASSE 1069 & ASSE 1070

Summary of Contents for MMV Series

Page 1: ... remove unions and gaskets from valve body prior to soldering 7 After soldering flush piping and install valve using filter washer on hot and cold water inlet and fiber washer on the mixed water outlet 8 Start up Open cold water supply then hot water supply Inspect for leaks 9 Adjust temperature to desired setting see Temperature Adjustment Section Watts recommends a maximum temperature of 110 F 4...

Page 2: ...ure Adjustment 1 Let the water flow for at least two minutes to allow supply temperature to stabilize 2 Calibrate the mixed water outlet temperature by placing a thermometer in the mixed water stream 3 To adjust the setting of the valve loosen locking cap screw with hex wrench see Figure 4 Cap must be lifted 1 4 to adjust temperature To increase the temperature turn coun terclockwise To decrease t...

Page 3: ...and cold side of Tempering valve see Product Guide for piping details D 1 Readjust valve temperature per installation instructions E 1 Clean check valves filters F 1 Reduce water velocity with pressure regulating valves F 2 Check flow required versus rated flow capacity of valve G 1 Open shutoffs or restore hot and cold supply G 2 Clean check valves and filters H 1 Stabilize water pressure with pr...

Page 4: ...ost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control This warranty shall be invalidated by any abuse misuse misapplic...