USER GUIDE 

GB 

HUMIDITY THERMOSTAT & ZONES PROGRAMMER 

o

Weekly and 12 zones programmer.

o

Permanent memory storage 

o

Regulation by internal or external probe in option. 

o

Heating, Cooling and humidity control. 

TECHNICAL CHARACTERISTICS

 

Measuring accuracy 

0.1°C  

Operating temperature 

0°C - 50°C 

Ambient temperature range 

5° C – 37° C in steps of 0.5° C 

Regulation characteristics 

Integral proportional band (PWM) or Static differential. 

Electrical Protection 

Class II   -   IP30 

Feeding and autonomy 

3 batteries AA LR06 1.5 V   /  > 2 years (alkaline batteries) 

Radio frequency and 
certifications 

433,92MHz, < 10mW 
CE. EN 300220-1,  EN 301489-1 

External probe in option 

CTN 10K 3M 

Program version 

To display the software version press the 

 during 3sec in anti freeze 

mode 

“Crf _.__”

 

DISPLAY 

1:

   

Function mode.  

2:

 

Heating mode indicator. 

3: 

Cooling mode indicator. 

4:

   

Ambient temperature indicator. 

5:

   

Ambient temperature if “4” lit up, current zone or 
temperature required. 

6:

   

Weekly program / Radio frame.  

7:   

Humidity level or time. 

8:

   

Current day of the week. 

9:

   

Low batteries.   

10: 

Holiday mode. 

OPERATING MODE DESCRIPTION 

Use 

 and 

 keys to change operating mode. 

Humidity Mode:

 

Use 

 and 

 to set the maximum humidity value (in relative humidity percent) of your room.  

The humidity drier output will be switch on when the current humidity is above this value. 
This output is controlled only in cooling mode “

Mod COOL

 ” or ‘

Mod AUTO

” in cooling. 

PPL IMP 1305 A 

INSTALLER’S PARAMETERS 

To access to the installation parameters menu, press 

during 10 s.

 

Use 

 and 

 keys to show the parameter to adjust. 

Press

 to toggle the parameter setting or edit the value. If the value starts to blink you can use 

and 

keys to adjust this value. Press 

and 

 keys at the same time to reset this value to the factory default value. 

Once you have adjusted the value press

 to validate this parameter value. 

When you have finished, go to « 

CrF Init

 » parameter and press 

to go back to the main menu.

 

 

Installation parameters: 

name 

Description 

Default setting 

Other possibility 

CrF Init 

Use this parameter to configure the thermostat with the receiver. 

J0 

°C or °F temperature display selection 

°C

°F

J1 

12h or 24h time display 

24h 

12h 

CH 

Numbers of zones installed on your installation 

12 

Adjustable « 

01 

» to

 

« 

12 

»

 

H.C 

Type of installation: 

Menu:

 The cold warm change is manually 

managed by the end user. (On the thermostat) 

Auto:

 The cold warm change is managed by the 

automatic reversible Heat pump. (Special input on 
the RF Receiver) 

Menu

Auto

J2 

Select

  Hot

 or 

CoLd

 to adjust : 

 if lit up =>

 adjust the heater parameters.

 

if lit up =>

 adjust the cooler parameters. 

Hot

CoLd

J5 

Anti-lock-braking function of the pump 
When the pump hasn’t worked on a particular day, 
start it up for one minute each day. 

 (adjustable in 

 & 

 in 

Menu 

position

)

 

 

Yes 

 

 

no 

 

J6 

Air or Floor temperature regulation selection.  
(if no Floor sensor, regulation will use Air sensor) 

Air

FLor

J7 

Selection of regulation type  

(adjustable in 

 & 

 in 

Menu 

position

)

 

Bp  

(PWM)

« 

hyst 

» 

static differential of 0.5°C 

Cy 

Selection of the proportional band duration in 
minutes 

(adjustable in 

 & 

 in 

Menu 

position

)

 

15  =>  

Slow system 
adapted to each 
heating type 

30  =>  

adapted to Heat 

pump control 

Heating application : 

Burner oil « 

20 

» 

Burner gas « 

10 

» 

Actuator  « 

10 

» 

Heat pump « 

20

» 

Cooling application : 

Heat pump/ Air conditioning « 

30

» 

Ventilate convector « 

10 

» 

On 

Minimal starting time in minutes 

(adjustable in 

 & 

 in 

Menu 

position

)

 

2  =>  

4  =>  

Adjustable, 

0

 to ½  

Cy

  

OF 

Minimal resting time between 2 heating cycles in 
minutes 

(adjustable in 

 & 

 in 

Menu 

position

)

 

3  =>  

4  =>  

Adjustable, 

0

 to 

½  Cy

  

bP 

Value of the proportional band (PWM) 

(adjustable in 

 & 

 in 

Menu 

position

)

 

2.0°C  =>  

4.0°C  =>  

Adjustable  

1

°C to

 6

°C 

A well insulated house 

1.5°C

 

In case of your house has not a 

good insulation increase this value. 

Ao 

Air sensor offset adjustment.  
Display measured Air sensor value. 

 No offset 

Adjustable 

+

 

12°C

 

Fo 

Floor sensor offset adjustment.  
Display measured Floor sensor value. 

 

No offset

Adjustable 

+

 

12°C

 

FL 

Floor temperature LOW limitation,  
Effective only if floor sensor present. 

(adjustable in 

 & 

 in 

Menu 

position

)

 

18°C =>  

18°C =>  

Adjustable 

5,0 °C

 to 

FH

 

FH 

Floor temperature HIGH limitation,  
Effective only if floor sensor present. 

(adjustable in 

 & 

 in 

Menu 

position

)

 

28°C =>  

37°C =>  

Adjustable 

FL

 

to

 37°C

 

GAP 

Value of the dead zones (only for “

Mod Auto

”) 

4,0°C 

Adjustable 

0,2°C

 to 

25 °C

 

dLY 

Time delay between the Heat and Cold 
commutation in minutes (only for “

Mod Auto

”) 

 60  

Adjustable 

1

 to 

240

 min 

CLr 

Press 

 during 5sec to reset your thermostat, all parameter will reload with default values. 