background image

10          IOM-ACV-110-10_6110-10 2115 

EDP#1917113 

© 2021 Watts

IOM-ACV-110-10_6110-10 2115 

EDP#1917113 

© 2021 Watts         11

Optional 

Xylan 

Coating

17A

6

1

2

3

4

5

7

8

9

11

12

13

14

15

16

17

18

10

Item

Description

Material

1

Pipe Plug

Lead Free Brass

2

Cover 

ASTM A536 65-45-12 Epoxy Coated Ductile Iron

3

Cover Bearing

ASTM A276 304 Stainless Steel

4

Stud with Cover Nut and Washer

ASTM A570 Gr.33 Zinc Plated Steel

5

Body

ASTM A536 65-45-12 Epoxy Coated Ductile Iron

6

Spring

ASTM A276 302 Stainless Steel

7

Stem Nut

ASTM A276 304 Stainless Steel

8

Lock Washer

ASTM A276 304 Stainless Steel

9

Stem Washer

ASTM A276 304 Stainless Steel

10

Diaphragm Washer

ASTM A536 65-45-12 Epoxy Coated Ductile Iron

11

Diaphragm*

Buna-N (Nitrile)

12

Disc Retainer

ASTM A536 65-45-12 Epoxy Coated Ductile Iron

13

Seat Disc* 

Buna-N (Nitrile)

14

Spacer Washer*  x5

NY300 Fiber*

15

Disc Guide

ASTM A743 CF8M (316) Stainless Steel

16

Shaft 

ASTM A276 304 Stainless Steel

17

Seat Ring**

ASTM A743 CF8M (316) Stainless Steel

17A

Seat Screw** (8" and Larger) 

ASTM A276 304 Stainless Steel

18

Seat Gasket*

Buna-N (Nitrile)

* Contained in Main Valve Repair Kit

**Note: 6 inch and Smaller Valves, Seat Ring is threaded

Installation: If unit is installed in any orientation other than 

horizontal (cover up) OR extreme space constraints exist, 

consult customer service prior to or at the time of order. 

NOTICE

ACV Assembly Diagram – Series LFM110-10

Summary of Contents for LFM110-10

Page 1: ... Control Valve 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the information provided You are required to consult the local building and plumbing codes prior to installation If the information provided here is not consistent with local building or plumbing codes the local codes shou...

Page 2: ... adequate clearance for valve servicing and maintenance Refer to valve servicing dimensions on next page Avoid installing valves 6 and larger in the vertical position main valve stem horizontal Automatic Control Valves ACVs are designed for horizon tal in line installation with the cover facing up main valve stem vertical Slow operation or premature stem and guide wear may occur if valve is not in...

Page 3: ...lve Tighten the fitting when liquid begins to vent See Figure 1 Step 4 Slowly open downstream isolation valve to establish flow through the system Globe Angle Size in 11 4 11 2 2 21 2 3 4 6 8 10 12 14 16 20 24 A in 16 16 20 22 22 24 32 34 38 44 48 52 56 56 B in 10 10 12 14 14 16 24 26 28 30 34 40 48 48 Size in 11 4 11 2 2 21 2 3 4 6 8 10 12 14 16 C in 16 16 20 22 22 24 32 34 38 44 48 52 D in 10 10...

Page 4: ...too slowly turn the adjustment screw OUT counterclockwise increasing the rate of opening See Figure 2B If the main valve is opening too quickly turn the adjustment screw IN clockwise decreasing the rate of opening See Figure 2A STEP 6 When installing float set angle similar to Figure 3 by adjusting F10 11 modulating float pilot linkage screw shown in Figure 4 4 IOM ACV 110 10_6110 10 2115 EDP 1917...

Page 5: ... specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm or tighten disc diaphragm assembly Test 2 Seat Seal Test 1 Close downstream isolation valve and install pressure gauges on an open inlet and outlet port of main valve 2 Open upstream isolation valve...

Page 6: ...2 1 2 turns open from full closed position Can be adjusted in field Main Valve will not close Closed isolation valves in pilot system Check isolation valves ensure open Diaphragm is damaged Conduct diaphragm seal test repair and replace if necessary Main valve stem assembly corroded damaged Inspect stem assembly clean replace if necessary Blockage in main valve Perform freedom of movement test if ...

Page 7: ...Remove cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require the installation of lifting eye bolts in order to facilitate cover removal installation ports are provided on the cover for this purpose 4 Remove the Disc and Diaphragm Assembly from the valve body ...

Page 8: ...brush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are threaded into the body of the valve and require a seat removal tool Figure 5 Table 1 details the tool dimensions for seat removal Valve seats 8 and larger are held in the valve body with stainless steel ca...

Page 9: ...Nuts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrity of the Seat Seal by following the Seat Seal Test procedure in previous section 12 Return valve to service by following instructions on the Technical Bulletin matching the valve function Size in 11...

Page 10: ...ess Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 13 Seat Disc Buna N Nitrile 14 Spacer Washer x5 NY300 Fiber 15 Disc Guide ASTM A743 CF8M 316 Stainless Steel 16 Shaft ASTM A276 304 Stainless Steel 17 Seat Ring ASTM A743 CF8M 316 Stainless Steel 17A Seat Screw 8 and Larger ASTM A276 3...

Page 11: ...IOM ACV 110 10_6110 10 2115 EDP 1917113 2021 Watts 11 NOTES ...

Page 12: ...not be responsible for any incidental special or consequential damages including without limitation lost profits or the cost of repairing or replacing other property which is damaged if this product does not work properly other costs resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances o...

Reviews: