background image

5

Servicing the Relief Valve

 

WARNING

!

Before to servicing the relief valve, it is mandatory to shut 

down water system by closing both the inlet and outlet 

shutoff valves and relieving pressure within the assembly by 

opening test cocks No. 2, No. 3, and No. 4.

DO NOT REMOVE SPIDER BUSHING FOR SERVICING

1.  Detach the activation module, if installed, from the flood sensor.
2.  Use a #2 Phillips screwdriver to remove the sensor from the 

relief valve.

3.   Disconnect the hose from the bottom cover plate to the  

relief valve.

4.   An O-ring seals the relief valve body to the main housing. 

Avoid tightening the connection beyond firm hand tightening. 

The relief valve should be removable by unscrewing the relief 

valve from the housing.

5.   Remove the cover plate of the relief valve by detaching the 

four connecting screws.

6.   Remove the rubber diaphragm from the relief valve. Notice 

how the diaphragm is configured so that it can be reinstalled 

in the same manner. The hard rubber tab in the diaphragm fits 

into a similar socket in the head of the piston. (See Figure A.)

7.   Hold the relief valve in both hands with the threaded end 

up and both thumbs on the head of the piston. Push up on 

the piston until the piston shaft with the attached E-clip is 

exposed. Remove the E-clip. (See Figure B.)

8.   Remove the piston and spring from the relief valve housing and 

thoroughly clean all parts including the diaphragm. Inspect all 

rubber parts for damage; if any are damaged, replace with 

new parts.

9.   Reassemble the relief valve in the reverse order of these 

instructions.

Figure B

Figure A

Summary of Contents for LFC500-FS Series

Page 1: ...l products must be retested once maintenance has been performed Corrosive water conditions and or unauthorized adjustments or repair could render the product ineffective for the service intended Regul...

Page 2: ...water authority approves the installation The assembly should be installed with adequate clearance around the valve to allow for inspection testing and servicing A minimum clearance of 12 should be b...

Page 3: ...ne See Figure C 5 Remove the check 2 module with the same instructions as in step 4 For servicing 6 checks see the maintenance instructions for sizes 8 to 10 6 To clean or inspect either check module...

Page 4: ...the service hole and thread in the service bolt by hand until it contacts the linkage See Figure A 4 Continue to thread in service bolt with the wrench until the service hole in the linkage is aligne...

Page 5: ...ewing the relief valve from the housing 5 Remove the cover plate of the relief valve by detaching the four connecting screws 6 Remove the rubber diaphragm from the relief valve Notice how the diaphrag...

Page 6: ...ock No 2 Close test cock No 4 Disconnect vent hose at test cock No 4 Open valves B and C bleeding to atmosphere Then closing valve B restores the system to a normal static condition Observe the pressu...

Page 7: ...Check Module O ring First Check Module Relief Valve Second Check Module Troubleshooting PROBLEM CAUSE SOLUTION Relief valve discharges water while system is not flowing Check 1 is fouled Remove and cl...

Page 8: ...rom the date of original shipment In the event of such defects within the warranty period the Company will at its option replace or recondition the product without charge THE WARRANTY SET FORTH HEREIN...

Reviews: