background image

•  Install backflow preventers in high-visibility locations to allow for 

immediate notice of telltale discharge or other malfunction. This 

location should also facilitate testing and servicing, and protect 

against freezing and vandalism.

•  Do not install a backflow preventer in a pit or vault. Ensure that  

all local codes and required safety provisions are met. An air  

gap below the relief port must be maintained so as to avoid  

flooding and submersion of the assembly, which may lead to a 

cross-connection.

•  Install a strainer ahead of the backflow preventer to protect all 

internal components from unnecessary fouling.

Do not install a strainer ahead of the backflow preventer on seldom-

used, emergency water lines (such as fire sprinkler lines). The strainer 

mesh could potentially become clogged with debris present in the 

water and cause water blockage during an emergency.

•  Consider using an air gap and a fabricated indirect waste line to 

accommodate normal discharge and nuisance spitting. Floor drains 

of the same size must be provided in case of excessive discharge.

•  Determine if a check valve is required ahead of the backflow preventer. 

When a backflow preventer is installed for dead-end service  

applications (such as boiler feed lines, cooling tower makeup, or 

other equipment with periodic flow requirements), discharge from 

the relief vent may occur due to water supply pressure fluctuation 

during static no-flow conditions. *See “Troubleshooting,” before 

installation.

•  Observe the direction of the flow arrows on the valve assembly. 

The backflow preventer is designed so that the critical level of the 

relief valve is positioned below the first check. This unique feature 

allows the valve to be installed either vertically or horizontally.

•  Follow guidelines for the specific installation option selected, that 

is, indoor, outside, or parallel. The installation procedure must 

comply with all state and local codes.

•  Before installation, thoroughly flush all pipelines to remove any  

foreign matter.

•  At the start-up of initial installation and after servicing, be sure the 

downstream shutoff is closed. Slowly open the upstream shutoff 

and allow the backflow preventer to fill slowly. Bleed air at each test 

cock. When the backflow preventer is filled, slowly open the down-

stream shutoff and fill the water supply system. This is necessary 

to avoid dislodging O-rings or causing damage to internal components.

•  Have the backflow preventer examined by a certified tester at the 

time of installation to ascertain that the assembly is in full working 

order and that it can be relied upon to protect the safe drinking 

water as per applicable standards.

First 

Check

Relief 

Valve

Second 

Check

LF909-QT-FS

2

Installation Guidelines

CAUTION

!

Summary of Contents for LF909-FS

Page 1: ...ion A retrofit sensor connection kit is available for existing installations See Add on and Retrofit Sensor Connection Kits on the last page How It Operates The unique relief valve construction incorporates two channels one for air the other for water When the relief valve opens the right channel admits air to the top of the reduced pressure zone relieving the zone vacuum The left channel then dra...

Page 2: ... or other equipment with periodic flow requirements discharge from the relief vent may occur due to water supply pressure fluctuation during static no flow conditions See Troubleshooting before installation Observe the direction of the flow arrows on the valve assembly The backflow preventer is designed so that the critical level of the relief valve is positioned below the first check This unique ...

Page 3: ...ng A discharge line should be piped from the air gap at the relief valve connection making sure there is adequate drainage Never pipe the discharge line directly into a drainage ditch sewer or sump The assembly should never be installed where any part of the unit could become submerged in standing water Consideration should be given to the installation of external support structure as applicable I...

Page 4: ...se needle valve A high red and open test cock No 2 2 Close test cock No 4 Disconnect the bypass hose yellow at test cock No 4 3 Open needle valves B low blue and C bypass yellow bleeding to atmosphere Then close needle valve B blue to restore the system to a normal static condition 4 Observe the pressure differential gauge If there is a decrease in the indicated value the No 1 check valve is repor...

Page 5: ...is attached with a bayonet type locking arrangement 3 Holding the check valve module in both hands rotate the assembly quarter turn This disengages the disc assembly spring and seat cover into individual components 4 Clean and reassemble the disc assembly or depending upon its condition discard and replace it with a new assembly from the service kit O rings should be cleaned or replaced as necessa...

Page 6: ...ver handy to reassemble the relief valve assembly Figure 2 Depress the assembly carefully guiding it against the 2 pound spring load When properly aligned the piston is in the cylinder bore Insert the screwdriver along the right channel wall positioning the screwdriver tip to the left of the relief valve O rings to hold the assembly in place Figure 3 Let go of the screwdriver and use both hands to...

Page 7: ...ound the piping system and or electrically isolate the device with plastic pipe immediately upstream and down stream of the device Valve improperly reassembled If valve is dis as sem bled during installation exercise caution when reinstalling check springs in their proper location Valve exhibits high pressure drop Fouled strainer Clean strainer element or replace Valve too small for flows encounte...

Page 8: ...ivation module with cable ground wire and power adapter Use this kit to activate the integrated flood sensor and enable flood detection capabilities on the relief valve of a new installation working with a BMS controller not included 88003058 FP RFK BF BMS CFS 1 11 2 BMS Sensor Retrofit Connection Kit Series LF909 Small Sizes to 1 Includes flood sensor sensor activation module with cable mounting ...

Reviews: