background image

4

 

Installation Continued

5. Remove the green circuit board terminal strip from the Control Unit by pulling straight out on the terminal strip. 

Figure 16

6.  Install wiring (The wire is installer supplied. Thermostat wire is acceptable.) between the green circuit board connector and the 

Power Supply, observing polarity, as shown on both the Power Supply and the control panel. [+ to + and – to –] 

Figure 17 

Maximum run of thermostat wire; 18 gauge – 75 feet; 20 gauge – 50 feet; 22 gauge – 35 feet.

Note:  

If remote alarm detection is desired, connection to the alarm circuit can be made using the normally open contacts provided on 

the terminal strip. These contacts are rated for 150mA. Do not exceed this amp range or damage to the Control Unit can occur. 

Exceeding the current rating will void the warranty. 

Figure 18

IMPORTANT! –

 Do not insert the Power Supply into the 120 VAC outlet until the installation is complete.

7. Insert the green circuit board connector into the Control Unit. 

Figure 19

8.  Check the position of the valve reset located on the front of the Control Unit. The slots should indicate the valve is in the open  

position. The 11 o’clock position is the open position. 

Figure 20

 open position; 

Figure 21

 closed position.

9. Turn on the water supply and check for leaks.
10. Insert the Power Supply into a suitable 120 VAC outlet. The status lamp on the Control Unit will be green.

IMPORTANT! –

 The outlet must be powered at all times; it must not be controlled by a switch.

11.  Turn on the electricity to the water heater. The water heater should operate normally.

Figure 19

Figure 20

Figure 21

Figure 16

Figure 17

Figure 18

Summary of Contents for FloodSafe WDS-SI Series

Page 1: ...er Detector Shutoff should be installed within 6 to 12 inches of the water heater on the cold water inlet supply pipe The Control Unit which houses the circuitry for the operation of the valve contains interlocking connectors for the Water Detector Pad the Power Supply and remote alarm and the Power Cutout Module The cables provided should not be cut or extended therefore remote installation is no...

Page 2: ...sary to remove the cover of the Control Unit to install the interconnecting cables To remove an interlocking cable use the supplied Pocket Screwdriver to depress the tab on the cable while pulling cable from its socket Figure 4 Important Interconnecting wires must not touch or be in close proximity to any flame or hot surface a If no drain pan exists install the Water Dam around the perimeter of t...

Page 3: ...f the cable Connect the cable from the Power Cutout Module Figure 14 Terminal C common to the SPARK terminal of the Electronic Control and NO normally open to the Pilot Electrode Assembly as indicated in Diagram 2 Figures 12 and 13 Note We have made every effort to provide all of the hardware required for a complete installation However the terminal connections used to connect the Pilot Electrode ...

Page 4: ... to the Control Unit can occur Exceeding the current rating will void the warranty Figure 18 IMPORTANT Do not insert the Power Supply into the 120 VAC outlet until the installation is complete 7 Insert the green circuit board connector into the Control Unit Figure 19 8 Check the position of the valve reset located on the front of the Control Unit The slots should indicate the valve is in the open ...

Page 5: ...3 If all of the above functions take place the unit can be reset To Reset the Control Unit 1 Remove the Water Detector Pad from the drain pan or Water Dam and wipe the moisture from the green circuit board 2 Wipe any water from the drain pan or Water Dam 3 Reposition the Water Detector Pad on the floor or in the drain pan 4 Turn the valve position indicator on the Control Unit to the open position...

Reviews: