background image

Watts Industries Italia Srl 

Watts EW089.308_en – rev.1 

Gas detection Control Unit – CIVIC1  

28/03/2011 

Gas detection systems for industrial environments 

2 of 4 

 

 

CIVIC1 control unit 
The control unit must be powered at 12 Vac/dc; use transformers 
with double insulation, sized for uninterrupted use for the power 
utilised (See Technical specifications). 
For connecting the relay output use wires with a minimum 
diameter of 1.5 mm

2

Prepare wiring connections according to the electrical diagrams 
contained in these instructions. 

 

UR13 or UR20S detector 

 

Prepare wiring connections according to the electrical diagrams 
contained in these instructions, using wires with a minimum 
diameter of 1.5 mm

2

 for a maximum length of 50 m. 

 
COMMISSIONING 

 

The CIVIC1 control unit and the UR13 or UR2S detectors are 
safety control devices, therefore they must not be tampered with; 
do not touch the sensor or the electronics for any reason 
whatsoever. Carry out the following controls: 

-

 

the power supply for the control unit must comply with the 
values provided (12 Vac/dc 

 10%) 

-

 

make sure the power consumed by any device connected to the 
relay terminals is below or the same as the maximum capacity 
of the contacts (See Technical specifications) 

-

 

make sure the consumption of any device connected to the 
open collector output terminals is below what is declared in the 
technical data 

-

 

the detector must be compatible with the type of gas to 
monitor and correctly connected to the control unit.

 

Depending on the type of detector to connect it is necessary to 
position jumpers E5 and E6 as follows: 

 
 
 
 
 
 
 
 
 
 
 
 

-

 

the operating mode (positive or negative logic) selected must 
be consistent with the system choices. As regards this, check 
the position of Jumper E1 (See Operation) 

-

 

the operating mode selected for the relay must be consistent 
with the system choices. As regards this, check the position of 
Jumper E2 (See Operation) 

-

 

test the gas alarm and the detector failure condition events 
(See Operation). 

 
OPERATION 

 

The Jumper E1 can be used to select the operating mode (positive 
or negative logic). 
The control unit signals its operating status through LEDs. 
Depending on the operating mode selected through Jumper E1, in 
a normal situation (no alarm), the LEDs, the OC output and the 
relay are as follows: 
positive operating logic:   LEDs on; relay energised, OC output = 
ON 
negative 

operating 

logic: LEDs off; relay de-energised, OC 

output= OFF 
If the negative operating logic is selected, the alarm relay can be 
permanently or impulse controlled, depending on the position of 
Jumper E2: 
 

 

Once the correct power is supplied, the control unit carries out the 
following phases in sequence: 
 
LED and buzzer tests (about 5 seconds) 

 

Whichever operating mode is selected, the LEDs will switch on in 
sequence and the buzzer will sound briefly. 
 
Warm-up of detector (about 1 minute) 

 

During this phase, which brings the detector up to the correct 
operating temperature, the gas detection system is not 
operational. During this phase, if the wiring connections are 
correct, the control unit display shows the following: 
 
 
 
 
 
 
 
 
 
 
 
 
Operating test (about 3 minutes) 

 

Once the detector warm-up phase is complete, the device enters 
the operating test phase. During this phase, all internal timing is 
reset to ease operating verification of the detector (alarm 
simulation). In this case, the control unit display shows the 
following: 
 
 
 
 
 
 
 
 
 
 
 
 
Keep the “Reset/Test” button pressed down for over 1 second to 
interrupt the operating test phase. To test the detector correctly, 
proceed as follows: 
 
Gas alarm test: 

 

Bring the test cylinder close to the detector grille and release a 
small amount of gas (caution: if the gas is aimed directly at the 
sensor, this will be permanently damaged). For CO testing of 
detector, smoke produced by combustion can be used. The control 
unit will signal the alarm as follows: 
 
 
 
 
 
 
 
 
 
 
 
 
Keep the “Reset/Test” button pressed down for 1 second to 
silence the alarm (if there is no gas remaining) and terminate the 
operating test phase. To restart the Test phase, just keep the 
relative button pressed down for about 6 seconds. 

 

Caution 

The repeated use or high concentration of 
interfering substances (alcohol, lighter fluid etc.) 
can cause permanent damage to the sensor and 
put the device out of order. 

 

 

Interface 

Positive logic 

Negative logic 

Power supply LED 

Green 

Flashing 1 Hz 

Flashing 1 Hz 

Failure LED 

Yellow 

On 

Off 

Gas alarm LED 

Red  

On 

Off 

Alarm buzzer 

 

No sound 

No sound 

Alarm relay 

 

Energised 

De-energised 

Failure output 

 

On  

Off 

 

 

Interface 

Positive logic 

Negative logic 

Power supply LED 

Green 

Flashing 2 Hz 

Flashing 2 Hz 

Failure LED 

Yellow 

On 

Off 

Gas alarm LED 

Red  

On 

Off 

Alarm buzzer 

 

No sound 

No sound 

Alarm relay 

 

Energised 

De-energised 

Failure output 

 

On  

Off 

 

E2

A

B

E2

A

B

E2

A

B

Po

sizio

ne

 A

Rel

è di

 al

la

rme

Comando per

m

anent

e

Po

sizio

ne

 B

R

elè

 d

i a

llar

m

e

Comando i

m

pul

si

vo

E1

A

B

E1

A

B

E1

A

B

Po

sizio

ne

 A

Logi

ca

 pos

iti

va

Po

sizio

ne

 B

Logi

ca

 n

egat

iv

a

E2

A

B

E2

A

B

E2

A

B

E2

A

B

E2

A

B

E2

A

B

Po

sizio

ne

 A

Rel

è di

 al

la

rme

Comando per

m

anent

e

Po

sizio

ne

 B

R

elè

 d

i a

llar

m

e

Comando i

m

pul

si

vo

E1

A

B

E1

A

B

E1

A

B

E1

A

B

E1

A

B

E1

A

B

Po

sizio

ne

 A

Logi

ca

 pos

iti

va

Po

sizio

ne

 B

Logi

ca

 n

egat

iv

a

 

 

Interface 

Positive logic 

Negative logic 

Detector alarm LED 

Red 

Off 

On 

Alarm buzzer 

 

Continuous sound 

Continuous sound 

Alarm relay 

 

De-energised 

Energised 
(permanently or 
pulsed depending 
on E2) 

Failure output 

 

Off  

On 

 

E3

A

B

E6

Posizione (default)

per Sonda URx13

E5

E5

Posizione per
Sonda URx20..

E6

E3

A

B

E3

A

B

E6

Posizione (default)

per Sonda URx13

E5

E3

A

B

E3

A

B

E6

Posizione (default)

per Sonda URx13

E5

E5

Posizione per
Sonda URx20..

E6

E3

A

B

E5

Posizione per
Sonda URx20..

E6

E3

A

B

E3

A

B

 

(default) position of 

detector UR13 

position of detector 

UR20S 

Posi

tion A 

Positive lo

gic 

Posi

tion B 

N

egati

ve

 logi

Posi

tion A 

Ala

rm re

la

Per

m

ane

nt co

ntr

ol

 

Posi

tion B 

Ala

rm re

la

Pul

se co

ntr

ol

 

Reviews: