background image

 

PPLIMW15175Ba 

-  In  a  second  time,  you  can  adjust  the  desired  setting 
temperature  with 

(-) 

or 

(+)

,  press

  (OK)

  to  start  the  function. 

(Default value 24°C) 

The

logo  will  blink  and  the  number  of  hours  /days  left  is 

displayed until the end of the period. 

If  you  want  to  stop  the  Timer  function  before  the  end,  set 

the  duration  period  to  “

no

”  with 

(-) 

key  or  use  the  navigation 

keys (◄) or (►). 

 

3.8.  Reversible mode 

 

 

 

The  reversible  mode  allows  you  to  choose  the  working  mode 
for your installation. 
By  pressing  on  (-)  or  (+)  keys,  the  selected  working  mode 
blinks and can be modified. The user can then choose: 

Hot

 : the installation operates in heating mode (winter) 

CLd

 : the installation operates in cooling mode (summer).  

Warning: this menu is available if user activates parameter 21 
in Installer’s advanced Menu (refer to chapter 8) 
During this selection, the status LED will be red color if heating 
is selected or green color if cooling is selected. 
By  pressing  (OK)  key,  you  validate  you  selection.  By  pressing 

(◄) or (►) key or the 

(

key

you come back to the current 

working mode of the thermostat.

 

 

Remarks: 

- This menu is only available if the parameter “21” has been set 
to “REv” (refer to chapter 8) 
- This mode is not available if thermostat is linked with a central 
(BT-CT02). 

4. 

Special functions 

4.1.  Key lock 

Use  this  function  to  prevent  all  change  of  your  settings  (In  a 
child room, public area…) 
 
-  To  activate  the  Key  lock  function,  first  press  maintain  the 
escape key 

(

and then press simultaneously on the edition 

key 

( )

- The “

” logo will be displayed on the screen.  

Repeat the same procedure to unlock the key board. 

 

4.2.  Open window function 

 

This  function  is  able  to  stop  heating  if  thermostat  detects  an 
unusual decrease of temperature (open window). 

 

Principle:

  

If  the  displayed  temperature  (internal  or  ambient  sensor) 
decreases by 3°C or more during a 5 minutes period (or less), 
the thermostat stops heating for 15 minutes. If the temperature 
continues decreasing, it continues to stop. 
During this stop, the room temperature will blink. 

Return to normal mode:  

The thermostat returns automatically to normal mode after the 
stop period. 
The  function  can  be  overridden  by  pressing  the 

(OK) 

button 

during the stop heating phase.  
The blinking temperature should stop to indicate the end of the 
detection. 

Special cases: 

- This function doesn't work if thermostat is in Floor regulation 
-  This  function  doesn't  work  if  thermostat  is  in  OFF  or 
Antifreeze Mode 
-  If  temperature  is  less  than  10°C,  thermostat  will  regulates  at 
10°C during the stop phase (refer to chapter 5, parameter 06) 
- This function doesn’t work in Cooling mode 
 

4.3.  Humidity measurement 

(

*

)

 

 

Thermostats  measure  the  humidity  in  the  air.  This  measure 
allows: 
-  To  regulate  the  humidity  in  the  air  (refer  to  parameter  34  in 
chapter 8) 
-  To  protect  your  system  against  condensation  (refer  to 
parameter 35 in chapter 8).

 

 

4.4.  Visualization 

 

With  this  function,  you  can  quickly  view  the  current 
temperatures  of  the  different  sensors  connected  on  your 
thermostat  (floor,  remote,  external).  To  do  so,  on  the  main 
screen, press several times on the escape key 

(

)

. This “scroll 

function” is only available on the main screen: 
 
You will see in the order of each press: 
1/ the setting temperature followed by the thermostat 
2/ the ambient temperature 
3/ if the external sensor is connected: the outside temperature 
4/ the humidity percentage (*) 
Remarks : 
- refer to chapter 1.2 for icon meanings 
-  If  Parameter  “

Sen

”  is  set  on  “

Air

”  (refer  to  chapter  8),  the 

remote sensor will be used as an external sensor. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

5. 

Parameter’s menu 

 
Your  thermostat  has  a  parameter’s  menu.  To  enter  in  this 
menu,  press  and  maintain  the  edition  key 

( )

  during  5sec. 

Then  parameter  menu  will  appear  and  first  parameter  screen 
will be displayed 

 

 

 
 
Now  you  can  select  a  parameter  which  must  be  adjusted  with 
the  navigation  keys 

(◄)

  or 

(►)

,  once  the  parameter  chosen, 

toggle the value with the 

(OK)

 key, modify it with 

(-) 

or 

(+)

 and 

confirm your adjustment with 

(OK)

To  leave  the  parameter  menu,  choose  the  parameter  « 

End

 » 

and press 

(OK

or Return key 

(

). 

 

N° 

Default value & other possibilities 

00 

RF INI:

 

Radio configuration

 

Radio  configuration  mode  for  wireless  communication 
(refer to chapter 2.2) 

01 

dEG:

 

Unit of the temperatures displayed

 

°C

  Celsius 

°F

  Fahrenheit 

02 

__:__

  Selection of the Time clock unit 

24H

 (24:00) 

12H 

(12:00 AM /PM) 

03 

dst:

 Daylight Summer time change Summer<->Winter 

YES

 

automatic 

change 

according 

to 

date. 

no

    no daylight summer time automatic change. 

04 

AirC

Calibration of the internal probe

 

The  calibration  must  be  done  after  1  day  working  with 
the  same  setting  temperature  in  accordance  with  the 
following description: 
Put  a  thermometer  in  the  room  at  1.5M  distance  from 
the  floor  (like  the  thermostat)  and  check  the  real 
temperature in the room after 1 hour. 
When  you  enter  on  the  calibration  parameter  “

no

”  is 

displayed  on  the  right  to  indicate  no  calibration  has 
made.  
To enter the value shown on the thermometer, use the 

(-) 

or 

(+)

 keys to enter the real value. Then, press 

(Ok)

 

to confirm.  
The message “

Yes

” should be displayed; the value will 

be stored in the internal memory. 
If  you  need  to  erase  a  calibration  press  on  the  escape 

key 

(

)

.

  

The old value will be erased and the message “

no

” will 

be displayed.  

* Pay attention:  

Only the heating element driven by the thermostat must 
be used during the complete step of the calibration.

 

05 

AMbC

 : 

Calibration of the external wired probe

 

Same  calibration  method  as  described  in  parameter  
“04 AirC” above.

 

06 

HG:

 

Anti-freeze  temperature

  used  in  Holiday  mode 

Default value 10°C. 
Use the 

(-) 

or 

(+)

 keys to change the anti-freeze setting 

temperature. Then press 

(Ok)

 to confirm. 

07 

ITCS: YES, no 

The Intelligent Temperature Control System will activate 
your  installation  in  advance  (2  hours  maximum)  to 
assure 

the 

desired 

temperature 

at 

the 

hour 

programmed following your weekly program. 
This  automatic  control  system  works  in  the  following 
way: 
When you start your thermostat for the first time, it will 
measure the time taken by your installation to reach the 
set  temperature.  The  thermostat  will  re-measure  this 
time  at  each  program  change  to  compensate  external 
temperature change & influence. You can now program 
your  thermostat  without  the  need  to  adjust  the 
temperature in advance because your thermostat does 
it automatically for you.

 

08 

Clr ALL

:  

Reset to Factory setting

 

Press  and  maintain 

(Ok) 

key  during  5s  to  reset  Set 

points  temperatures  and  user  parameters  in  this  menu 
to  factory  default  settings.  User  programs  will  also  be 
resetted. 

 Pay attention:

  

Ensure you that you have all necessary elements to re-
setup your installation before using this function. 

09

 

Displayed  only  if  the  BT-DRF-02  is  linked  with  a 
multizones receiver

  

CHAn— 

--: number of the linked zone 

10 

Software version 
VErS ___ 

11 

End

Exit the parameter’s menu 

Press 

(OK) 

key to exit installation parameter menu and 

return to normal operation.

 

 

6.  Technical characteristics 

Environmental: 
Operating temperature: 
Shipping and storage 
temperature:

 

 
0°C - 40°C  
 
-10°C to +50°C 

Electrical Protection 
Installation Category 
Pollution Degree 

IP30 
Class II 

Temperature precision 

0.1°C  

Setting temperature range 
Comfort, Reduced 
Holiday (Antifreeze) 
Timer

 

0,5°C step 
5°C to 37°C 
0,5°C to 10,0°C 
5°C to 37°C 

Regulation characteristics 

Proportional Band (PWM 
2°C/10min)  
or Hysteresis 0.5°C 

Power Supply  
Operating life 

2 AAA LR03 1.5V Alkaline 
~2 years 

Sensing elements: 
Internal & External (option) 

 
Internal: NTC 10k

 at 25°C 

External: NTC 10k

 at 

25°C  (ß = 3950) 

Radio Frequency 

868 MHz, <10mW.  

Software version 

Showed in parameter 
menu. 

Vers

 xxx

 

Compatible receivers 

BT-M6Z02 RF 
BT-FR02RF 
BT-WR02RF / BT-WR02HC 
BT-PR02RF 
Other receivers can be 
compatible : check on the 
instruction manual of your 
receiver 

CE Directives 

Your product has been 
designed in conformity with 
the European Directives. 

R&TTE 1999/5/EC 
EMC 004/108/EC 
RoHS 2011/65/EU 

Product conformed to :  
Classification :  
Contribution :  

UE 811/2013 and 
2010/30/UE  
IV 
(2%) 

 
 
 
 
 

7. 

Troubleshooting & Solution 

My BT DRF-02 doesn’t start 

Batteries 
Problem 

 
- Check if the protection sticker on the 
batteries is removed. 
- Check the batteries orientation.  
- Check the capacity of the batteries 
 

My BT DRF-02 Led, blinks in Red 

 
Problem on 
sensors 
 
 

 

 The logo blinks (air sensor) 

- Contact your installer or seller. 

 The logo blinks (Floor sensor) 

- Check the connection of the sensor. 
- Disconnect the sensor, and check it with 
an ohmmeter (the value must be around 
10kohms) 
 

Batteries level 
is too less 

 

 The logo blinks (Batteries) 

- Replace the batteries. 
 

Humidity 
measurement 
problem (*) 

The logo 

 blinks and the thermostat 

displays “Err” 

-  Contact your intaller 

My BT DRF-02 seems work correctly but the heating or 

the cooling doesn’t work correctly 

Output 

 
On the receiver: 
- Check the good reception of RF signal 
- Check the connections. 
- Check the power supply of the heating 
element. 
- Contact your installer. 
 

RF  
communication 

 
- Check the following points : 
- The receiver must be put at a 
minimum distance of 50cm of all others 
electrical or wireless materials (GSM, 
Wi-Fi..) 
- The receiver shouldn’t be fixed on a 
metallic part or too close of hydraulic 
pipes… (Copper…) 
 

Configuration 

 

The logo blinks : 

- Cooling request is made by the 
central (BT-CT02) but the thermostat 
doesn’t allow (refer to parameter 21 
chapter 8). 

Humidity 
protection (*) 

The logo blinks: 

- humidity regulation is activated (refer to 
parameter 

34

 in chapter 8) 

- condensation is detected (refer to 
parameter 

35

 in chapter 8)

 

My BT DRF-02 seems work correctly but the 

temperature in the room was never in accordance with 

the setting temperature. 

Program 

 
- Try to calibrate your thermostat (refer 
to user menu parameter 

04

- Contact your installer, to check & 
adjust the regulation parameters with 
your heating system. 
 

 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

8. 

Advanced installer’s parameter menu 

In  order  to  enter  in  the  menu,  press  on  the  escape  key 

 

 

during 5 seconds 

 

 
The display with the first parameter appears ( « rEGU »).

 

- Once you entered in the menu, go to the parameter which you 
want change by using the keys 

(◄)

 or 

(►)

.  

 
-  Use  the  keys 

(+) 

or

  (-)

  to  edit  and  modify  and  confirm  by 

pushing the 

(OK) 

key. 

 
- To leave the parameter menu, go to the parameter “

End

” and 

press the 

(OK) 

key. 

 
 

 
 
 
 

Parameters 

Installer’s Advanced Menu 

N° 

names 

Description of the parameter 

Factory value 

Other possibility 

20 

REGU 

Selection of the sensor used for the 
regulation. 

“AIR” 

Internal ambient 

sensor 

“amb” 

External ambient sensor 

Following option aren’t available 

with all receivers 

“FLR” 

Floor sensor regulation  

“FL.L” 

Air regulation with floor limitation 

possibilities  

(refer to parameters 25&26) 

21 

MOde 

Working mode selection of the thermostat 

“Hot” 

Heating mode

 

“Cld” 

Cooling mode 

“rEv” 

reversible menu activation

 

“Aut” 

Automatic mode 

21 

(**) 

Cld 

Use this option if you want to allow the 
zone to work in cooling mode 

“yes” 

Function activated 

“no” 

Function deactivated 

22 

 

AirS 

View of the measured values of the 
internal sensor.  

“__._”  °C/°F 

23 

AmbS 

View of the measured values of the 
external (Ambient) sensor.  

“__._”°C/°F 

24 

RecS 

View of the measured values of the floor 
sensor connected to the receiver.  

“__._”°C/°F 

25 

FL.Lo 

Lower limit of the floor temperature.  

“no” 

The lower 

limitation is not 

used 

From 5°C to 

“FL.Hi”                  

26 

FL.Hi 

Upper limit of the floor temperature.  

“no” 

The upper 

limitation is not 

used

 

From 

“FL.Lo”

 to 40°C 

27 

reg 

Selection of regulation type. 

“bp” 

Proportional band 

(PWM) 

“hys” 

Hysteresis (On/Off) 

28 

UF1 

Concrete choice. 

“uf1” 

For liquid concrete 

with low thickness  

< 6cm 

“uf2” 

For traditional concrete with 

thickness  

> 6cm 

29 

Bp1 

Floor covering choice. 

“Bp1” 

For tiling 

“Bp2” 

For wood parquet (floating or not) 

30 

Uir 

Pilot wire function for French Market 
application: 
Use this option if your installation has the 
pilot wire installed in combination with an 
energy saver. 

“yes” 

Function activated 

“no” 

Function deactivated 

31 

min 

Minimal value of the setting range. 

5.0°C

 

From 5°C to 15.0°C

 

32 

MAX 

Maximal value of the setting range. 

37.0°C

 

From 20°C to 37.0°C

 

33 

Uin 

Automatic open window detection.  

(Refer to chapter 4.2) 

“yes” 

Function activated 

“no” 

Function deactivated 

34(*) 

rH 

Percentage value of the humidity setting 

55%

 

From 0% (“no”) to 100% 

35(*) 

dEv 

Anti-condensation function 

(when condensation is detected, cooling 
system is stopped or/and dehumidifier is 
activated)

 

“yes” 

Function activated 

“no” 

Deactivated function

 

36 

Clr EEp 

All parameters will be reloaded with the 
factory value. 

Press on the 

(OK) 

key during few seconds. 

37 

End 

To exit the installer’s menu 

Press on the 

(OK) 

to exit. 

 

(*): concerns version with humidity sensor 
(**): concerns thermostat if it is linked with a central (BT-CT02) or with a BT-M6Z02 RF 
 