background image

Setting the Sustaining Control

STEP 1

Slowly open downstream isolation valve to establish flow through 

the system.

STEP 2

Setting the Sustaining Control requires lowering the upstream pres-

sure to the desired minimum sustained pressure.

STEP 3

Leave the downstream isolation valve full open and close the up-

stream isolation valve until the inlet pressure drops to the desired 

setting.

STEP 4

Adjust the Sustaining Control screw IN, clockwise, until the inlet 

pressure begins to increase, or OUT, counterclockwise, to de-

crease, stopping at the desired pressure (See Figure 2).

STEP 5

Allow pressure to stabilize.

STEP 6 

Fine-tune the sustaining setting as required as detailed in STEP 4.

STEP 7

Open upstream isolation valve to return to normal operation.

4          IOM-A-ACV-920-01-15_620-01-15   2115 

EDP# 1917050 

© 2021 Watts

IOM-A-ACV-920-01-15_620-01-15   2115 

EDP# 1917050 

© 2021 Watts         5

Figure 2 

PV20C — Pressure Sustaining Control

Clockwise to increase inlet 

pressure

Counterclockwise to decrease 

inlet pressure

Summary of Contents for AMES 920GD-01-15

Page 1: ...n 2 Setting the Pressure Controls 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the...

Page 2: ...sure in the upstream zone falls below the pilot setting the valve modulates toward a closed position sustaining pressure in the upstream zone The valve will close if necessary until upstream pressure...

Page 3: ...does not include a bleed valve bleed air by loosening a fitting on the valve or a plug at the highest point of the valve as sembly STEP 5 Pressure the line by opening the upstream isolation valve slow...

Page 4: ...the desired setting STEP 4 Adjust the Sustaining Control screw IN clockwise until the inlet pressure begins to increase or OUT counterclockwise to de crease stopping at the desired pressure See Figure...

Page 5: ...flow control allows free flow into the cover and restricted flow out of the cover of the main valve If valve opening is too slow turn the adjustment screw OUT counterclockwise increasing the rate of...

Page 6: ...cification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm or...

Page 7: ...st opening speed control to verify functionality adjust as required Standard setting for open ing speed control is 1 1 2 2 1 2 turns open from full closed position Can be adjusted in field Main Valve...

Page 8: ...e cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require the...

Page 9: ...h or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are threaded...

Page 10: ...in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrity o...

Page 11: ...Steel 9 Stem Washer ASTM A276 304 Stainless Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile...

Page 12: ...sulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no control...

Reviews: