background image

Size (in)

3

4

6

8

10

12

16

20 & 24

P/N

0677-01

0677-01

0677-02

0677-03

0677-04

0677-05

0677-09

0677-11

8.  Replace Seat Disc, Diaphragm and Spacer Washers provided in Main Valve repair kit (refer to Table 2 or 3 for correct repair kit part 

number). Re-assemble in the reverse order of disassembly.

9.    

 

Re-Install Disc and Diaphragm Assembly in the valve, taking care not to damage the lower guide area in the center of the valve    

  seat.

10.  Re-install Cover Spring. Replace Valve Cover and tighten Cover Nuts in a crossing pattern to ensure even distribution. Test the Disc 

and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section.

11.  Test the integrity of the Seat Seal by following the Seat Seal Test procedure in previous section.
12.  Return valve to service by following instructions on the Technical Bulletin matching the valve function.

Size (in)

1

 

1/4

1

 

1/2

2

2

 

1/2

10 

12 

14 

16 

P/N

0677-01

0677-01

0677-02

0677-03

0677-04

0677-05

0677-06

0677-07

0677-08

0677-09

0677-10

0677-11

Table 3: Reduced Port Valve (605GD/605AD) Repair Kits

Table 2: Full Port Valve (905GD/905AD) Repair Kits

10          IOM-A-ACV-920-01_620-01   2115 

EDP# 1917052 

© 2021 Watts

IOM-A-ACV-920-01_620-01   2115 

EDP# 1917052 

© 2021 Watts         11

Summary of Contents for Ames 620GD

Page 1: ...2 Setting the Pressure Controls 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica tions to the...

Page 2: ...ude the optional opening speed control when used for Backpressure applications When the Model valve is located in line connecting two distribution zones the valve acts as a Pressure Sustaining Control...

Page 3: ...o 21 2 turns from full closed position STEP 2 To ensure proper operation any trapped air will need to be bled off the valve cover during startup If your ACV includes a bleed valve use a flat head scre...

Page 4: ...d close the up stream isolation valve until the inlet pressure drops to the desired setting STEP 7 Adjust the Sustaining Control screw IN clockwise until the inlet pressure begins to increase or OUT c...

Page 5: ...g IF INSTALLED Opening Speed Flow Control Adjustment The Opening speed flow control allows free flow into the cover and re stricted flow out of the cover of the main valve If recovery of pres sure is...

Page 6: ...specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm...

Page 7: ...ly by partially opening from full closed position Improperly configured opening speed control if equipped Adjust opening speed control to verify functionality adjust as required Standard setting for o...

Page 8: ...move cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require...

Page 9: ...rush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thread...

Page 10: ...ts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrit...

Page 11: ...el 9 Stem Washer ASTM A276 304 Stainless Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iro...

Page 12: ...resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no cont...

Reviews: