SETTING THE SURGE CONTROL 

Note: Surge Control is set at a higher PSI than the 

Pressure Reducing Control.

STEP 4

Open downstream isolation valve partially to establish flow 

through the valve, observing downstream pressure change. In-

crease of pressure should stop below the desired surge pressure 

setting.

STEP 5

Gradually open downstream isolation valve until full open.

SETTING THE PRESSURE REDUCING CONTROL

STEP 1

Adjust the Pressure Reducing Control to the desired pressure set 

point by turning the adjustment screw OUT, counterclockwise 

until downstream pressure decreases to the desired setpoint (See 

Figure 3).

STEP 6

Adjust the Surge Control by turning the adjustment screw IN, 

clockwise, to increase, or OUT, counterclockwise, to decrease, 

the downstream pressure surge set-point (See Figure 2).

Counterclockwise to DECREASE 

downstream pressure

Clockwise to INCREASE-

downstream pressure

Figure 3 

CP15 — Pressure Reducing Control

Clockwise to INCREASE 

downstream pressure surge 

set-point

Counterclockwise to DECREASE 

downstream pressure surge set-

point

Figure 2 

PV20C — Surge Control

4          IOM-A-ACV-912-11_612-11   2115 

EDP# 1917038 

© 2021 Watts

IOM-A-ACV-912-11_612-11   2115 

EDP# 11917038 

© 2021 Watts         5

Summary of Contents for Ames 612GD-11

Page 1: ...tion 2 Setting the Pressure Reducing Control 3 Maintenance Schedule 6 Trouble Shooting Guide 6 Valve Disassembly Instructions 8 ACV Schematic 11 Local building or plumbing codes may require modifica t...

Page 2: ...valves ensure valve disc does not contact the main valve 6 Provide adequate clearance for valve servicing and maintenance Refer to valve servicing dimensions on next page 7 Avoid installing valves 6...

Page 3: ...4 16 24 26 28 30 34 40 48 48 Size in 11 4 11 2 2 21 2 3 4 6 8 10 12 14 16 C in 16 16 20 22 22 24 32 34 38 44 48 52 D in 10 10 12 14 14 16 24 26 28 30 34 40 STEP 2 To ensure proper operation any trappe...

Page 4: ...pressure set point by turning the adjustment screw OUT counterclockwise until downstream pressure decreases to the desired setpoint See Figure 3 STEP 6 Adjust the Surge Control by turning the adjustm...

Page 5: ...ise increasing the rate of closing Setting the Pressure Sustaining Control Step 1 Setting The Relief Sustaining Control requires lowering the upstream pressure to the desired minimum sustained pressur...

Page 6: ...specification sheets for approximate cover capacity A continuous flow of water from the open port indicates a damaged diaphragm or loose disc diaphragm assembly Disassemble valve and replace diaphragm...

Page 7: ...ly by partially opening from full closed position Improperly configured opening speed control if equipped Adjust opening speed control to verify functionality adjust as required Standard setting for o...

Page 8: ...move cover nuts and washers 3 Remove the cover If cover is not free to be removed loosen it by tapping upward along its outside edge with a dull cold chisel pic tured above a Large valves may require...

Page 9: ...rush or by using a Mineral Dissolving Solution Inspect parts for wear and replace if necessary 7 Inspect valve seat If seat is not damaged removal is not necessary Valve seats 6 and smaller are thread...

Page 10: ...ts in a crossing pattern to ensure even distribution Test the Disc and Diaphragm Assembly for smooth travel by following the Freedom of Movement Test procedure in previous section 11 Test the integrit...

Page 11: ...el 9 Stem Washer ASTM A276 304 Stainless Steel 10 Diaphragm Washer ASTM A536 65 45 12 Epoxy Coated Ductile Iron 11 Diaphragm Buna N Nitrile 12 Disc Retainer ASTM A536 65 45 12 Epoxy Coated Ductile Iro...

Page 12: ...resulting from labor charges delays vandalism negligence fouling caused by foreign material damage from adverse water conditions chemical or any other circumstances over which the Company has no cont...

Reviews: