EXAMPLES:
1. A 40 foot length of combustion air pipe and 1 sharp 90° elbow plus two termination 90° elbows
add up to 40 ft. + 10 ft. + (2 x 10 ft.) = 70 equivalent ft. (21.3 m).
2. A 30 foot length of combustion air pipe and 2 sharp 90° elbows plus two termination 90°
elbows add up to 30 ft. + (2 x 10 ft.) + (2 x 10 ft.) = 70 equivalent ft. (21.3 m).
2.3.
COMMON COMBUSTION AIR PIPE SIZING
Refer to Figures 9 and 10 for typical common combustion air inlet installation. The maximum length is
the sum of the equivalent straight length of horizontal runs, vertical runs, and fittings of the individual
combustion air connector and the common combustion air pipe. The required diameter lengths for a
given Modulex total BTU/hr. Input are shown in Table 4, below.
TABLE 4: Typical Common Combustion Air Run Lengths
TOTAL
BTU/HR
INPUT
(UP TO AND
INCLUDING)
COMMON
VENT
DIAMETER
EQUIVALENT COMMON VENT LENGTHS EXAMPLES
MAXIMUM LENGTH
INDIVIDUAL
CONNECTOR
PLUS COMMON VENT
EQUIVALENT FT (M)
Sharp 90°
Elbow
Equiv. Ft (m)
Sweep 90°
Elbow
Equiv. Ft (m)
45° Elbow
Equiv. Ft (m)
WYE or
Termination
Tee or
Vent Cap
Equiv. Ft (m)
606,000
4”
(102 mm)
10 ft.
(3.05 m)
5 ft.
(1.5 m)
5 ft.
(1.5 m)
5 ft.
(1.5 m)
100 ft.
(30.5 m)
1,284,000
6”
(152 mm)
10 ft.
(3.05 m)
N/A
5 ft.
(1.5 m)
5 ft.
(1.5 m)
100 ft.
(30.5 m)
2,407,500
8”
(203 mm)
10 ft.
(3.05 m)
N/A
5 ft.
(1.5 m)
5 ft.
(1.5 m)
100 ft.
(30.5 m)
3,825,000
10”
(254 mm)
10 ft.
(3.05 m)
N/A
5 ft.
(1.5 m)
5 ft.
(1.5 m)
100 ft.
(30.5 m)
5,355,000
12”
(305 mm)
10 ft.
(3.05 m)
N/A
5 ft.
(1.5 m)
5 ft.
(1.5 m)
100 ft.
(30.5 m)
6,885,000
14”
(358 mm)
10 ft.
(3.05 m)
N/A
5 ft.
(1.5 m)
5 ft.
(1.5 m)
100 ft.
(30.5 m)
9,180,000
16”
(407 mm)
10 ft.
(3.05 m)
N/A
5 ft.
(1.5 m)
5 ft.
(1.5 m)
100 ft.
(30.5 m)
The chart above shows equivalent pipe lengths of the fittings for the common combustion air pipe.
See section 2.2 for equivalent lengths for fittings for the individual boiler connector.
The maximum equivalent length shown is the sum of the equivalent length of the longest individual
connector plus the equivalent length of the common combustion air pipe. If the maximum equivalent
length exceeds 100 equivalent feet, contact your AERCO sales representative or AERCO
International for design assistance and approval.
It is important to use a WYE as a means to connect the individual combustion air pipe into the
common combustion air pipe. This will ensure the least amount of pressure drop. Do NOT use a
TEE, 90°, or 45° elbow.
The maximum pressure drop of the vent is also 100 equivalent feet (30.5 m). Note that this does
NOT mean that the allowed combined pressure drop between the vent and combustion air is 200
equivalent feet (61 m). That is, the vent cannot go above 100 equivalent feet (30.5 m), even if the
combustion air is less than 100 equivalent feet, and vice versa.