Modulex Light Commercial Series
CHAPTER 4: Installation Instructions
OMM-0158_A
• 6/28/2022 Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
42
of
120
4.21 Flue Exhaust Piping To Vent
In a condensing boiler, the flue exhaust is evacuated at a very low temperature (maximum of
about 183°F - 84°C). Thus, it is necessary that the chimney be impermeble to the condensate of
the combustion products and is made of corrosion resistant materials.
The different joints must be well sealed and equipped with suitable gaskets in order to prevent
the escape of condensate and prevent the ingress of air.
To determine the proper cross section and height dimensions of the flue exhaust piping, it is
necessary to make reference to national and local rules.
In order to prevent the formation of ice during the operation, the temperature of the internal wall
of the flue exhaust system should not be below 32 °F (0 °C) throughout its length.
For efficient venting of the combustion exhaust and to address condensation due to lower external
temperatures, ensure that combustion condensation is discharged into the boiler condensate tray
or into another separate collection pan according to the installation.
A test nipple, for measuring combustion gases, should be installed onto the first three feet of the
exhaust manifold flue. To do this, a hole with a diameter of
0.83‘‘is drilled in a convenient location
for testing and the test nipple hardware assembled to the flue pipe, as shown in Figure 4-22.
Figure 4-22: Installation of Test Nipple into Flue Manifold Piping
C A U T I O N !
Damage caused by mistakes in installation, failure to complete the instructions as written, or the
improper use of the flue system are not the responsibility of the supplier.