Innovation Hot Water Hot Water Boiler User Manual
- INTERNATIONAL
CHAPTER 4 – INITIAL START-UP
OMM-0120_0A
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
51
of
174
GF-128-I
Phone: 800-526-0288
11/15/2016
4.2.3 Accessing the Analyzer Probe Port
The unit contains a 1/8” NPT port at the rear of the exhaust manifold. This port is located above
the condensate drain connection as shown in Figure 4-2. Prepare the port for the combustion
analyzer probe as follows:
Accessing Analyzer Probe Port
1.
Refer to Figure 4-2 and remove the 1/8” NPT plug from the rear of the exhaust manifold.
2.
If necessary, adjust the stop on the combustion analyzer probe so it will extend mid-way
into the flue gas flow. DO NOT install the probe at this time
Figure 4-2. Analyzer Probe Hole Location
4.2.4 Connecting Multimeter to Flame Detector
During Combustion Calibration, the flame strength generated by the flame detector is measured
using a multimeter set to the µA scale. The flame detector is mounted on the intake manifold
flange as shown in Figure 4-3.
Proceed as follows to set up the multimeter to measure the flame strength current:
EXHAUST
MANIFOLD
VENT PROBE
PORT WITH
1/8” (3.18 mm)
NPT PLUG
CONDENSATE
DRAIN