Innovation Hot Water Hot Water Boiler User Manual
- INTERNATIONAL
CHAPTER 3 – OPERATION
Page
40
of
174
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0120_0A
11/15/2016
Phone: 800-526-0288
GF-128-I
3.5 SETUP MENU
The Setup menu permits the operator to enter the unit password (159) which is required to
change the menu options. To prevent unauthorized use, the password will time-out after 1 hour.
Therefore, the correct password must be reentered when required. In addition to permitting
password entries, the Setup menu is also used to enter date and time, and units of temperature
measurements. A view-only software version display is also provided to indicate the current
Control Box software version.
A full description of each item appears in Table A-2 of Appendix A – Innovation Menu Item
Descriptions.
Table 3-3. Setup Menu
Menu Item
Display
Available Choices or
Limits
Default
Minimum
Maximum
1
Password
0
9999
0
2
Language
English
English
3
Time
12:00 am
11:59 pm
4
Date
01/01/00
12/31/99
5
Unit of Temp
Fahrenheit or Celsius
Fahrenheit
6
Comm Address
0
127
0
7
Baud Rate
2400, 4800, 9600, 19.2K
9600
8
OnAER Mode
Ethernet or SD Card
Ethernet
9
Upload Timer
0
9999 Sec
0
10
Unit Alpha
E, G, H, R, N or A
A
11
Unit Year
0
99
0
12
Unit Serial #
0
9999
0
13
Software
Ver 0.00
Ver 9.99
Current software version
3.6 CONFIGURATION MENU
The Configuration menu permits adjustment of the Internal Setpoint (Setpt) temperature
regardless of whether the valid password has been entered. Setpt is required for operation in
the Constant Setpoint mode. The remaining options in this menu require the valid password to
be entered, prior to changing existing entries. This menu contains a number of other
configuration settings which may or may not be displayed, depending on the current operating
mode setting.
A full description of each item appears in Table A-3 of Appendix A – Innovation Menu Item
Descriptions.
NOTE
The Configuration menu settings shown in the table below are
Factory-Set in accordance with the requirements specified for
each individual order. Therefore, under normal operating
conditions, no changes will be required.