APPENDIX A – INNOVATION MENU ITEM DESCRIPTIONS
Page
128
of
174
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0120_0A
11/15/2016
Phone: 800-526-0288
GF-128-I
Table A-2: Setup Menu Item Descriptions
Table A-2:
SETUP MENU ITEM DESCRIPTIONS
See section 3-5 for a range of choices and the default values.
MENU LEVEL & OPTION
DESCRIPTION
1
Password
Allows password to be entered.
Once the valid password (159) is entered, options in the
Setup, Configuration and Tuning Menus can be modified.
2
Language
English only
3
Time
Displays time from 12:00 am to 11:59 pm.
4
Date
Displays dates from 01/01/00 to 12/31/99
5
Unit of Temp
Permits selection of temperature displays in degrees
Fahrenheit (°F) or degrees Celsius (°C).
6
Comm Address
For RS-485 communications (0 to 127). Default address is 0.
RS232 should have its own (programmable) password.
7
Baud Rate
Allows communications Baud Rate to be set (2400 to 19.2K).
8
OnAER Mode
Allows the selection of OnAER data destination medium
between Ethernet and SD Card
9
Min Upload Timer
Sets the time between OnAER Heartbeat data transmissions
10
Unit Alpha
Sets the Alpha portion of a unit serial number
11
Unit Year
Sets the Year portion of a unit serial number
12
Unit Serial #
Sets the Number portion of a unit serial number
13
Software Version
Identifies the current software version of the control box (Ver
0.0 to Ver 9.9).