Eurotherm 3508 Controller Guide
Section 9: TRANSITION FROM LOCAL TO REMOTE SETPOINT CONTROL
TAG-0101
• DRAFT Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST Page
10
of
10
9 TRANSITION FROM LOCAL TO REMOTE SETPOINT CONTROL
1. Press
until the
Control Loop 1 (Lp1)
Function
Block is displayed.
2. Press
▲
or
▼
until
Setpoint (SP)
is displayed.
3. Press
until the
Alternate Setpoint Enable (Alt SP En)
is displayed.
4. Press
▲
or
▼
to select YES.
5. The
Remote
Beacon will appear on the Display.
6. Write the
Remote Setpoint
to
Modbus Holding Register 485 (AltSP).