Combustion Calibration

 

GAS SUPPLY PRESSURE TEST 

1.

 

Close the manual gas shutoff valve.  

2.

 

Remove the front cover. 

3.

 

Turn inlet pressure port D screw three turns CCW. 

4.

 

Connect manometer to port D. 

5.

 

Open the manual gas shutoff valve. 

6.

 

Check gas pressure does not exceed 13”

 W.C. Adjust upstream 

gas regulator as needed. 

7.

 

Turn power switch ON. 

8.

 

Generate heat demand: press 

(boiler/water heater) or 

R

 

(indirect water heater) to its maximum setting. 

9.

 

Set Para 2200 (AM 399-1000) or 2010 (AM 199/250) to HIGH 

10.

 

Check gas pressure is between 3”

-

13” W.C. Adjust upstream 

gas regulator as needed. 

11.

 

Return Para. 2200 or 2010 to OFF 

12.

 

Close the manual gas shutoff valve. 

13.

 

Disconnect the manometer. 

14.

 

Turn port D screw CW until snug and check it for any gas 

leaks. 

  

  

COMBUSTION CALIBRATION 

1.

 

Follow vent pipe manufacturer’s instruction to install combustion analyzer probe 8” after the flue gas exhaust connection.

 

2.

 

Start unit per procedure on this page. 

3.

 

Set unit to standby: Press 

A

 (boiler) or 

S

 

(water heater) until “OFF” is displayed

 

4.

 

Set Para 2201 (AM 399-1000) or 2010 (AM 199/250) to HIGH 

5.

 

Generate demand: Press 

C

 (boiler) or 

R

 

(water heater) until setpoint is above “OFF” (e.g. 90F)

 

6.

 

Wait 2-3 min. for CO2 to stabilize. 

7.

 

Compare CO2 reading with high fire range in Table below, making sure to use the range for gas type in use. If CO2 reading is outside the range, 

use screw E (2.5mm Allen) to adjust: CW to reduce CO2, CCW to increase CO2. Adjust in small increments and wait for CO2 to stabilize in between 
readings. 

8.

 

Set Para 2201 OR 2010 to LOW. 

9.

 

Wait 2-3 min. for CO2 to stabilize. 

10.

 

Compare CO2 reading with low fire range in Table below, making sure to use the range for gas type in use. 

If low fire CO2 reading is outside the 

range, STOP the unit and call the Factory service department. 

 

11.

 

Set Para. 2201 or 2010 to OFF. 

12.

 

AM 399-1000: repeat steps 3-9 for burners 2, 3 and 4 as applicable, using parameters 2202-2204 to calibrate each burner in turn. 

13.

 

Close the combustion analyzer probe.  

  

Summary of Contents for Aerco AM Series

Page 1: ...1 Neutralizer media 4 Adjustable foot 1 Outdoor sensor boiler models only 1 Piping kit for circulation pump AMRI models only shipped loose ALCOVE CLOSET INSTALLATIONS Follow rules on clearances ventin...

Page 2: ...ss Steel Polypropylene CPVC PVC For Alcove Closet Installation use Al29 4C only Do not use PVC exhaust for applications where return water temperature 145F See O M for additional information Polypropy...

Page 3: ...ngle unit application relocate supply temperature sensor from boiler header to system piping Multiple unit application install Cascade header temperature sensor in the system piping see AERCO Cascade...

Page 4: ...Fri 8 am 5 pm EST Page 4 of 7 BOILER APPLICATIONS WATER HEATING APPLICATIONS with Integrated Tank The condensate drain must slope down and away from the boiler into a drain it must be installed accord...

Page 5: ...y Terminals 101 102 PE Low Water Cut Off Terminals 103 104 Primary Pump boiler loop Terminals 113 114 Constant Setpoint Enable Disable if employed otherwise jumped Terminals 10 11 Set Para 2003 0 Outd...

Page 6: ...ion Module on each unit AM399 1000 factory installed AM199 250 optional Refer to the AM Series MODBUS User Manual GF 146 MB for wiring and setup details Controls Panel Button Functions To access Insta...

Page 7: ...install combustion analyzer probe 8 after the flue gas exhaust connection 2 Start unit per procedure on this page 3 Set unit to standby Press A boiler or S water heater until OFF is displayed 4 Set Pa...

Reviews: