Installation, Maintenance, & Repair 

Series 919 and LF919

Reduced Pressure Zone Assemblies

Sizes: 

1

4

" – 2" (8 – 50mm)

919QT

RP/IS-919

NOTICE

For Australia and New Zealand, line strainers should be installed 

between the upstream shutoff valve and the inlet of the backflow 

preventer.

Its important that this assembly be tested periodically in compliance 

with local codes, but at least once per year or more as service con-

ditions warrant. If installed on a fire sprinkler system, all mechanical 

checks, such as alarm checks and backflow preventers, should be 

flow tested and inspected internally in accordance with NFPA 13 

and NFPA 25.

Testing

For field testing procedure, send for IS-TK-DL, IS-TK-7, 

IS-TK-9A, IS-TK-99E AND IS-TK-99D.
For other repair kits and service parts, send for PL-RP-BPD.
For technical assistance, contact your local Watts 

representative.

WARNING

!

Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information 

can result in death, serious personal injury, property 

damage, or damage to the equipment.
Keep this Manual for future reference.

Installation Guidelines

Reduced Pressure Zone 

Assemblies Indoor Installation

For indoor installations, make sure the Series 919 and LF919 is 

easily accessible to facilitate testing and servicing. Do not install in 

concealed locations. If the location of the Series 919 and LF919 is 

parallel and close to the wall, make sure the test cocks are easily 

accessible, and the drain line can adequately drain if required. An air 

gap and drain line (see literature ES-AG/EL/TC) are piped from the 

relief valve connection as shown, allowing evidence of discharge to 

be clearly visible and preventing the occurrence of water damage. 

Air Gap

Strainer

Meter

Indoor Installation

12" (300mm) Minimum 

(refer to local codes)

Watts

1

4

" – 2" (8 – 50mm) 919

Local building or plumbing codes may require modifications 

to the information provided.  You are required to consult the 

local building and plumbing codes prior to installation.  If this 

information provided here is not consistent with local building 

or plumbing codes, the local codes should be followed. This 

product must be installed by a licensed contractor in accor-

dance with the local codes and ordinances.

WARNING

!

Need for Periodic Inspection/Maintenance:

  This product must 

be tested periodically in compliance with local codes, but at least 

once per year or more as service conditions warrant.  All products 

must be retested once maintenance has been performed.  Cor-

rosive water conditions and/or unauthorized adjustments or repair 

could render the product ineffective for the service intended.  Regular 

checking and cleaning of the product’s internal components helps 

assure maximum life and proper product function. 

WARNING

!