Zone Valve Control 305V

Installation Manual

Call

Valve

Open

Zone Valve Control 305V

Five Zones with Priority

H3027A

Power

Priority

System

Pump

Zone 1

Zone 2

Zone 3

Zone 4

Zone 5

RoomResponse

TM

The Zone Valve Control 305V connects up to five thermostats and operates a circulator and zone valves to provide 
heating to a zoned hydronic heating system.

•  RoomResponse

TM

 signal

•  Compatible with all low voltage thermostats
•  Unlimited zone expansion
•  Zone priority
•  Priority override
•  Pump exercising
•  Post purge
•  Away signal shared between tekmar thermostats

Features

•  LED for each zone, priority, end switch and 

RoomResponse

TM

•  Four ground screws
•  Top, bottom and back conduit knockouts
•  Fuses protect transformers and pumps
•  Two spare fuses included
•  CSA approved

Summary of Contents for 779655030518

Page 1: ...culator and zone valves to provide heating to a zoned hydronic heating system RoomResponseTM signal Compatible with all low voltage thermostats Unlimited zone expansion Zone priority Priority override...

Page 2: ...if not avoided could result in minor or moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read manual and all...

Page 3: ...eedle nose pliers Wire stripper 18 AWG LVT solid wire low voltage connections 14 AWG solid wire line voltage connections Four 1 8 1 wood screws 1 Zone Valve Control 305V 2 Spare fuses located in cover...

Page 4: ...lle d whe n u s i n g p o w e r stealing thermostats e g Thermostat T4 N B1 PS 305V V1 V2 V3 V4 V5 Away C R Rh W Away C R Rh W Away C R Rh W R W R W MOD X X tN4 T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T...

Page 5: ...aling Thermostat T4 Generic Bi Metallic Strip Thermostat V1 2 Wire Zone Valve V2 3 Wire Zone Valves e g Taco 570 V3 V4 4 Wire Zone Valve Away C R Rh W Away C R Rh W R W R W MOD X X tN4 T1 T2 T3 T4 T5...

Page 6: ...ay C R Rh W Away C R Rh W T T Away C R Rh W MOD X X tN4 T1 T2 T3 T4 T5 T6 A DHW C R W BOILER T STAT 1 T STAT 2 T STAT 3 tN4 A C R W tN4 A C R W T STAT 4 tN4 A C R W T STAT 5 tN4 A C R W T STAT 6 EXPAN...

Page 7: ...he boiler If using a single Switching Relay set to Master When using multiple Switching Relays and or Zone Valve Controls set one control to Master and set all other controls to Member The boiler end...

Page 8: ...ration Boiler Make Model Required Adapter Supplied by boiler manufacturer 0 10 V dc 4 20 mA DIP Switch Mod Max Dial for Boiler Design Temperature 120 F 140 F 160 F 180 F Aerco AM series Not required 0...

Page 9: ...Change Energy Management setting Central Heat Modulation Source to 4 20 mA Change Energy Management setting Central Heat 4 20 mA Setup 4 mA Water Temperature to 80 F 26 5 C 9 10 22 23 5 6 16 17 2 U 1...

Page 10: ...tpoint source to 4 20mA Enter boiler password Set Parameter Setpoint source to 4 20mA Lochinvar Knight Lochinvar FTXL NTI Trinity LX Riverside HeatStation NTI Trinity Fire Tube 305V 305V 305V 305V 305...

Page 11: ...305V 305V 1 4 1 2 5 6 Connect to the Viessmann Extension Module EA1 Plug 0 10V Zone Valve Control 305V Five Zones with Priority Literature Submittal 305V_C Installation Manual 305V_D Job Record 305V_...

Page 12: ...made by Pur chaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser s sole responsibility and obligation Purchaser shall indemnify and hold tekma...