10
For additional cross-connection control information, send for F-50 brochure.
Symptom
Cause
Solution
1. Check valve fails to hold
a. Debris on check disc
Disassemble and clean
1.0 PSID minimum
sealing surface
b. Leaking gate valve
Disassemble and clean or repair
c. Damaged seat disc or
Disassemble and replace
seat
o-ring
d. Damaged guide holding
Disassemble clean or replace
check
open
e. Weak or broken spring
Disassemble and replace spring
2. Chatter during flow
a. Worn, damaged or
Disassemble and repair or
conditions
defective guide
replace guide
3. Low flows passing
a. Mainline check fouled
Disassemble and clean
through
mainline
valve
b. Meter strainer plugged
Disassemble and clean
c. Damaged mainline seat
Disassemble and replace
disc or seat
d. Broken mainline spring
Disassemble and replace
Troubleshooting Guide
Series 009 and LF009