Press menu button until the Adjust Menu is displayed. Press item button 
to locate the desired setting.

Item Field

Range

Access

Description

Set to

ADJUST

-60 to 45°F

(-51.0 to 7.0°C)

Default = 10°F

(-12.0°C)

Installer

OUTDOOR DESIGN

Typically set to the temperature of the coldest day of 
the year. The outdoor air temperature used in the boiler 
heating curve is used to determine the boiler target 
temperature. 

EMS2,

EMS1,

4-20

0-10,

2STG,

1STG

Default = 1STG

Installer

BOILER TYPE

The type of boiler connected to the control.
1STG = single one-stage on-off boiler
2STG = single two-stage on-off boiler
0-10 = 0-10 V (dc) modulating boiler
4-20 = 4-20 mA modulating boiler
EMS1 = tekmar boiler staging controls
EMS2 = Viessmann modulating boilers with 
OpenTherm

70 to 200°F

(21.0 to 93.5°C)

Default = 180°F 

(82.0°C)

Installer

BOILER DESIGN

The supply water temperature required for the boiler 
zones to heat the building on the typical coldest day 
of the year. Recommendations:
High mass radiant floor = 120°F (50°C)
Low mass radiant floor = 140°F (60°C)
Fancoil or air handling unit = 190°F (90°C)
Copper fin-tube convector = 180°F (80°C)
Radiators = 160°F (70°C)
Low profile baseboard = 150°F (65°C)

11. Critical Settings

Summary of Contents for Tekmar tekmarNet2 House Control 400

Page 1: ...at Load Zone Valve Load Floating Action VA Control Load VA Total Zone Load 2 Transformer must exceed VA Sensor with bottom entry wiring Sensor with rear entry wiring Sensor mounted onto 2 x 4 electric...

Page 2: ...e 4 Vlv C Com Zone 1 Zone 2 Zone 3 Zone 4 tN2 tN2 tN2 tN2 tN2 tN2 tN2 tN2 Sensors No Power Call Call tN4 C Mod dc mA Boil Exp Setpoint DHW R C Input Power H8005D Use at least 167 F 75 C conductors Sta...

Page 3: ...stem Saving ENERGY SAVING INDICATOR Displays when the system is saving energy See the Saving Indicator section WWSD WWSD Displays when the system is in Warm Weather Shut Down F C minhr sec F C HOURS M...

Page 4: ...year The outdoor air temperature used in the boiler heating curve is used to determine the boiler target temperature EMS2 EMS1 4 20 0 10 2STG 1STG Default 1STG Installer BOILER TYPE The type of boiler...

Page 5: ...DHW to pump grounds N L Boil System Pump DHW Pump Pump Power L Strip wires 1 2 inch 13 mm Installed wires are not removable 12 18 AWG red black black Capteurs de tuyau Capteurs ext rieurs Capteur en p...

Page 6: ...Exp Setpoint DHW R C Input Power H8005B Made in Canada Use at least 167 F 75 C conductors Stage 2 Stage 1 Vannes de zone 24 V ca Transformateur 009 Appel de DHW partir du r servoir DHW Aquastat facul...

Page 7: ...CONOMIE D NERGIE S affiche lorsque le syst me conomise de l nergie Reportez vous la section de l indicateur d conomie WWSD WWSD S affiche lorsque le syst me s arr te cause d un sur chauffage C F minhr...

Page 8: ...ur utilis e dans la cuve de chauffage de la chaudi re est utilis e pour d terminer la temp rature de consigne chaudi re EMS2 EMS1 4 20 0 10 2STG 1STG Par d faut 1STG Installateur BOIL TYPE TYPE DE CHA...

Page 9: ...grounds N L Boil System Pump DHW Pump Pump Power L Strip wires 1 2 inch 13 mm Installed wires are not removable 12 18 AWG red black black Sensores de ca er as Sensor de exterior Pozo del sensor Seguro...

Page 10: ...N2 tN2 tN2 tN2 Sensores sin potencia tN4 C Mod dc mA Boil Exp R C H8005D Stage 2 Stage 1 Expansi n de la caldera tN4 Caldera moduladora Potencia de entrada Usar con conductores que como m nimo soporte...

Page 11: ...ahorrando energ a V ase la secci n del Indicador de ahorro WWSD WWSD DESCONEXI N POR CLIMA C LIDO Muestra cuando el sistema se encuentra trabajando bajo el m todo de desconexi n por clima c lido F C...

Page 12: ...exterior que se utiliza en la curva la calefacci n de la caldera determinar la temperatura buscada de la caldera EMS2 EMS1 4 20 0 10 2STG 1STG Predeterminada 1STG Instalador BOIL TYPE TIPO DE CALDERA...

Reviews: