The Dimming Curve LED will blink according to load type below.
CURVE/LOAD TYPES
Dimming Curve
Load Type
Curve 1 - 1 blink
followed by a pause,
then repeats.
Incand/MLV/ELV/LED/
Neon/cold cathode
Curve 2 - 2 blinks
followed by a pause,
then repeats.
2 wire fluor (Advance
Mark X or equal)
Curve 3 - 3 blinks
followed by a pause,
then repeats.
3 wire Lutron (Hi-Lume
or Eco-10)
Step 3: Repeat steps 1 and 2 for the second load.
Step 4: Exit Dimming Curve Selection
To exit Dimming Curve Selection simply release the Load
Override Button.
IMPORTANT NOTE: THE DIMMING CURVE MUST
BE SET FOR PROPER OPERATION.
Load On/Off/Dimming
Override Buttons
Load Status: Blue LEDs
Dimming Curve: Yellow LED
Red
LED
Config
Button
Dimming Curve Button
Button Selection Location and LEDs
DIMMING CURVE SELECTION
Dimming Curve Selection Procedure
The Dimming Curve button allows selection of the appropriate
curve for the connected load type.
By default the curve is factory set to curve 1 which is for
incandescent, MLV, ELV, LED, and neon/cc loads.
Step 1: Load Selection
Press and hold the Load button for the load that you wish to
configure.
The lights will dim down/up in a continuous cycle.
Step 2: Curve Selection
While continuing to press and hold the Load Button, Tap
and release the Dimming Curve Button to select the correct
curve
for the connected load type (see Curve/load types).
Each subsequent tap of the dimming curve button will cycle to the
next curve. This will be indicated by the frequency at which the
yellow Dim Curve LED is blinking (see Curve/load types).
0341373638
Serial
Number
Room
Controller
Load
Control
LMRC-222
3
4
0575852231
Master
0341373638
LMRC-222
1
2
A
B
A
B
0574762112
In a DLM local network
with only LMRC-222
room controllers, the
LMRC-222 with the
highest serial number
is the Master, carrying
Load 1 and 2. The next
highest serial number
would have Load 3 and
Load 4, and so forth.
Load A ON/OFF/Dim button
Blue LED
ON when
load is ON.
Load button:
Press &
release for
ON/OFF.
Press & hold
to Dim.
Load B ON/OFF/Dim button
PLUG n
’ GO OPERATION (P
nG)
Plug n’ Go supports the most energy efficient control
strategy. For example, if at least two loads, one switch
and one occupancy sensor are connected to the DLM local
network, the system operates load A as Automatic ON,
Automatic OFF and load B as Manual-On, Automatic-Off.
See DLM device Quick Start Guides to determine how each
device affects the PNG operation of the LMRC-222.
Load Control Arbitration
To take full advantage of automatic PnG configuration,
review these simple rules about load control arbitration.
After the room controllers are connected to the DLM Local
Network and powered up they automatically negotiate
to determine which controller becomes the Master and
assigns the load numbers for each load output on the DLM
Local Network.
The Master is the controller with the highest serial
number. The LMRC-222 has two load outputs.