background image

LightSaver

®

Controller

Model #- LS-100XA & XB

Santa Clara, CA 95050
(800) 879-8585

S

ORDERING INFORMATION

S

WARRANTY INFORMATION

The Watt Stopper

®

, Inc. warranties its products to be free of defects in

materials and workmanship for a period of five years.  There are no obligations
or liabilities on the part of The Watt Stopper

®

, Inc. for consequential damages

arising out of or in connection with the use or performance of this product or
other indirect damages with respect to loss of property, revenue, or profit, or
cost of removal, installation or reinstallation.

Putting a Stop to Energy Waste

Santa Clara CA 95050 (800) 879-8585

86-0403-00

LS-100XA
LS-100XB

A277E-P
A347D-P
S120/277/347E-P

LightSaver

®

 Controller (10-200FC range)

LightSaver

®

 Controller (50-1000FC range)

Power Pack: 277VAC, 60Hz, 20A ballast
Power Pack: 347VAC, 60Hz, 15A ballast

A120E-P

Power Pack: 120VAC, 60Hz,

 

20A ballast/13A incandescent

Slave Pack:  120/277VAC, 60Hz, 20A ballast

 

347VAC, 60Hz, 15A ballast 

Installation Instructions

Call (800) 879-8585 For Technical Support

S

SPECIFICATIONS

Voltages 24VDC
Power Supply

Watt Stopper Power Pack

Control Output

120mA maximum

Time Adjustment

3 seconds-5 minutes

Sensitivity Adjustment

Minimum-Maximum

Light Level Adjustment

LS-100XA

10-200FC

LS-100XB

50-1000FC

Call (800) 879-8585 For Technical Support

S

TROUBLESHOOTING

Lights will not turn on:                                           

1. Make sure the power has been turned on at the circuit breaker.
2. Check all wire connections between the sensor and power pack.
3. If there is still a problem, check to see if there is 24VDC at the sensor (RED 

and BLK).

• If 24VDC is present, replace the sensor.
• Is 24VDC is not present, make sure the power pack is functioning. 

4. If lights still do not go on, call (800) 879-8585 for technical support.

Lights will not turn off:                                           

1. Is the LED GREEN or RED?

• If RED, make sure that the override jumper is not installed.
• If GREEN, see next step.

2. To test if unit is operating properly, set the time delay to minimum. 

Lights should turn off after 3 seconds.

3. If lights still do not go off, call (800) 879-8585 for technical support.

ON-Bypass                                                            

The ON/Bypass pin is the rectangular cutout located next to the sensitivity
adjustment. When the bypass jumper is inserted in this slot, lighting systems are
overridden into the ON position. They remain on as long as the ON/Bypass pin
remains inserted.

S

SETTING LEVELS

Setting the LS-100X should be performed in daylight conditions where the
ambient light level is high enough that the lights would be kept off due to
enough light. A footcandle meter is helpful.

1) The pre-set time delay of three minutes is an excellent starting point for 

most applications. You can shorten the delay in areas such as hallways, 
lobbies, and warehouses where users won’t be confused by a sudden 
change in lighting levels. The time delay adjustment is at its maximum 
when the adjustment is turned fully counterclockwise (as seen from the 
back of the unit).

2) To begin the adjustment process, turn the “S” adjustment fully clockwise 

(to the right) and the “D” adjustment fully counterclockwise (to the left). 
The LED should be red. The lights should  be on.

3) Next, turn the “S” counterclockwise until the LED turns green. This 

represents the OFF level, or the lighting level at which the lights will be 
turned off.

4) To adjust the deadband level turn the “D” adjustment clockwise about 

50% until it is pointing straight up.  If you notice that the lights seem to 
be cycling on and off too much, turn “D” slightly clockwise and continue 
this until the cycling stops.  If you think the space is getting too dark 
before the lights turn back on, turn “D” slightly counterclockwise.

5) Once all adjustments have been made, permanently mount the sensor to 

the mounting surface with the screws provided. (See 

INSTALLATION

for more information on the final installation process.)

Reviews: