9
4.3.1 Function List
Function
Fn xx
Description
Set Unit
Range
Factory
Setting
Remark
Capacity 0
Capacity
selection
1
1-18
*3
Accel. /
1
Accel. Time 1
0.1 sec
0.1-3600 sec
10 sec
*1
Decel. time
2
Decel. Time 1
0.1 sec
0.1-3600 sec
10 sec
*1
Remote
Operation Select
3
xx00 : FWD/STOP, REV/STOP
xx01 : FWD/REV, RUN/STOP
xx10 : 3 wire control mode
x0xx : REV command enable
x1xx : REV command disable
0xxx : Setting frequency will remain at last output frequency when
inverter stops and Fn_11 = 3
1xxx : Setting frequency will be 0 (zero) when inverter stops and
Fn_11 = 3
0000
Parameter Lock
Select
4
xxx0 : Enable (Fn 17 - 25)
xxx1 : Disable (Fn 17 - 25)
xx0x : Enable (Functions except Fn 17 - 25)
xx1x : Disable (Functions except Fn 17 - 25)
0000
V/F Pattern
5
V/F pattern selected
1
0-18
9 / 0
*4
Freq. Limit
6
Freq. output upper limit
0.01 Hz
0-400 Hz
60 / 50
*4
7
Freq. output lower limit
0.01 Hz
0-400 Hz
0 Hz
Speed Agreed
8
Up-to desired frequency setting
0.01 Hz
0-400 Hz
0 Hz
detection
9
Up-to frequency setting detection
width
0.01 Hz
0-30 Hz
0 Hz
Control Mode
Select
10
0 : Digital operator Control
1 : Remote Control
0
Freq. Command
Method Select
11
0 : Run by Fn 25
1 : Run by VR on digital operator
2 : Run by VR on TM2 (terminal 12-14) or analog signal
3 : Run by multi-function input freq. Command (terminal 6-8)
0