![Watlow F4T Installation And Troubleshooting User’S Manual Download Page 24](http://html2.mh-extra.com/html/watlow/f4t/f4t_installation-and-troubleshooting-users-manual_3701562024.webp)
Watlow F4T Install & Troubleshooting
•
21
•
Chapter 2 Install and Wire
Output Connections
(cont .)
Tri-Process/Retransmit (High Density)
FMHA - FAAA - A _ _ _
volts - / current -
volts + / c
F1
H1
F2
H2
F3
H3
volts - / current -
volts + / c
volts - / current -
volts + / c
•
0 to 20 mA into 400Ω maximum load
• 0 to 10V
Î
(dc) into 4 kΩ minimum
load
• Outputs are scalable
• Output supplies power
• Each output can be independently set
for voltage or current
• Output may be used as retransmit or
control
negative
volts +
or
c
0 to 10 V
F2
H2
0 to 10 V
F3
H3
0 to 10 V
0 to 20 mA
F1
H1
Not Used
Not Used
volts +
or
c
volts +
or
c
negative
negative
0 to 20 mA
0 to 20 mA
Switched DC / Open Collector FM [M, L] A - _ CCA - A _ _ _
dc -
dc +
W2
Y2
Switched DC
• Output 1 and 2, 30 mA dc
maximum supply current not to
exceed 40 mA combined when
both outputs are used
• Short circuit limited to <50 mA
• 22 to 32V
Î
(dc) open circuit
voltage
• Use dc- and dc+ to drive exter-
nal solid-state relay.
• DIN-A-MITE compatible
Open Collector (Output 1 only)
• 100 mA maximum output cur-
rent sink
• 30V
Î
(dc) maximum supply
voltage
• Any switched dc output can use
the common terminal.
• Use an external class 2 or *SELV
power supply to control a dc
load, with the load positive to
the positive of the power sup-
ply, the load negative to the
open collector and common to
the power supply negative.
• *Safety Extra Low Voltage
Switched DC
FM [M, L] A - _ [C] [C] A - A _ _ _
dc +
dc -
common
24V
X_
W_
Y_
Note:
Total current of 40 mA not to be
exceeded if both outputs are used.
Open Collector
FM [M, L] A - _ [C] _A - A _ _ _
Load
Power Supply
dc -
common
24V
X1
W1
Y1
dc (open collector)
dc
common
X1
W1
Y1
Anderson-Bolds ~ 216-360-9800