Watlow Controls 

EHG CL User’s Guide

EHG CL Error Codes (cont.)

Display

Description Possible 

Cause

Corrective 

Action

[Ahi]

Alarm High

Process temp exceeds set point by 
value greater than alarm high setting

• 

Set HTA value to correct high 
temperature alert value

[Alo]

Alarm Low

Process temp below set point by value 
greater than alarm low setting

• 

Set LTA value to correct Low 
temperature alert value

[E91]

Communications Queue 
Full

Communications buffer overfl ow

• 

Contact Technical Support at 
1-507-494-5656

[E10]

EEPROM Error

EEPROM memory space fails CRC 
check (checksum for parameter space)

• 

Contact Technical Support at 
1-507-494-5656

[E11]

CRC Error

Flash memory space fails CRC check 
(checksum for program space)

• 

Contact Technical Support at 
1-507-494-5656

[E12]

CPU Clock Error

Clock frequency is < 5 MHz or > 13.1 
MHz

• 

Contact Technical Support at 
1-507-494-5656

[E13]

Stack Overfl ow

Stack has overfl owed

• 

Contact Technical Support at 
1-507-494-5656

[E15]

AI Function Error

Analog reference is < 1.82 or > 2.06 
volts

• 

Contact Technical Support at 
1-507-494-5656 

[E16]

Process Comparison 
Error

Limit and control sensor readings 
differ by value greater than process 
comparison value

• 

Check setting of Proces Com-
parison Value

• 

Set Process Comparison Value 
to correct value

• 

Check wiring of sensors

[E17]

Data Store Error

Data store functions are not set up

• 

Check setting of Process Com-
parison Value

• 

Check wiring of sensors

[E20]

Base control fi rmware 
ID not supported

Base control fi rmware is not compat-
ible with Display Module fi rmware

• Check 

fi rmware compatibility 

between Base Control and 
Display Module. Revision 20.0  
and greater for Base Control 
and Display Module are com-
patible for EHG2-AAAA-0000.

Summary of Contents for EHG CL Series

Page 1: ...erature controller and safety limit Process temperature output 10 amp NO ARC relay Safety limit 10 amp relay On off and PID temperature control algorithm Up graded via communications to PID algorithm...

Page 2: ...to 0 C 32 F to SLA setting 150 C 302 F 34 unsigned integer RWE No Dis play Heat Output Power Read via Modbus communications the present heat output power level 0 to 100 0 22 unsigned integer R No Dis...

Page 3: ...19 200 16 384 38 400 17 9 600 16 unsigned integer RWE tU tU Temperature Units Select the temperature scale F F 4 C C 5 C 17 unsigned integer RWE rpp rPP Restore Programmed Parameters Restore factory...

Page 4: ...on on off off Ambient Alarm Abt 85 C on on off off Health Check Error Normal Operating Range Limit High Set Point SLA Closed Loop Set Point Closed Loop Set Point Temperature Alarm Hysteresis Alarm Hys...

Page 5: ...1 507 494 5656 E12 CPU Clock Error Clock frequency is 5 MHz or 13 1 MHz Contact Technical Support at 1 507 494 5656 E13 Stack Over ow Stack has over owed Contact Technical Support at 1 507 494 5656 E1...

Page 6: ...l is cleared when the process value is outside of the proportional band Integral Int is measured in minutes per repeat A low integral value causes a fast integrating action Proportional plus Integral...

Page 7: ...r 4800 0021 With the control facing you this connector is on the right side L1 Switched black L2 white yellow red yellow red 1 3 4 5 7 8 6 2 Heater Limit Thermocouple Process Thermo couple Thermocoupl...

Page 8: ...parts which upon examination prove to be defective within the warranty period specified This warranty does not apply to damage resulting from transportation alteration misuse or abuse WARNING To avoi...

Page 9: ...nity EN 61000 4 4 2011 Electrical Fast Transient Burst Immunity EN 61000 4 5 2006 Surge Immunity EN 61000 4 6 2008 Conducted Immunity EN 61000 4 8 2009 Power frequency magnetic field immunity EN 61000...

Page 10: ...ebsite www watlow co uk From outside The United Kingdom Tel 44 115 964 0777 Fax 44 115 964 0071 Asia and Paci c Watlow Singapore Pte Ltd 16 Ayer Rajah Crescent 06 03 04 Singapore 139965 Tel 65 6773 94...

Reviews: