Watlow DIN-A-MITE Style B User Manual Download Page 3

WATLOW DIN-A-MITE Style B User's Manual

3

DIN-A-MITE B Ordering Information

To order, complete the code number on the right with the information below:

Style B

= solid-state power controller

D B _   _   -   _   _   _   _   -   _   _   _   _

Phase

1

= single-phase, 1 controlled leg

2

= 3-phase, 2 controlled legs

3

= 3-phase, 3 controlled legs (for 4-wire wye)

8

= 2 independent zones (input control C or K)

9

= 3 independent zones (input control C or K)

Cooling and Current Rating Per Pole

0

= Natural convection standard DIN rail or panel heatsink

Line and Load Voltage

02 = 24 to 48V

Å

(ac)

24 = 120 to 240V

Å

(ac)

60 = 277 to 600V

Å

(ac)

Input Control Signal

C0 = 4.5 to 32V

Î

(dc) contactor

K1 = 22 to 26V

Å

contactor

K2 = 100 to 120V

Å

contactor

K3 = 200 to 240V

Å

contactor

F0 = Proportional 4 to 20mA

Alarm

0

= No alarm

S = Shorted SCR Alarm (not available with phase options 8 or 9 above)

User Manual Language

0

= English

1

= German

2

= Spanish

3

= French

Custom Part Numbers

00 = Standard part
XX = Any letter or number, custom options, labeling, etc.

Current Rating Table

Model

Current 

at 50°C (122°F)

DB10

35A

DB20, DB80

25A

DB30, DB90

17A

Note:

• Recommended fusing options to meet 200KA SCCR, type 1 and 2 approved.  All other fuse and SCR combinations 

are defaulted to 5KA SCCR per UL508A and NEC guidelines.

Output Rating Curves

0

5

10 15 20 25 30 35 40 45 50 55 60

25

30

35

40

45

50

55

60

65

70

75

80

90

85

Current (Amps) into a Resistive Load

Maximum Internal Enclosure Ambient Temperature (

°

C)

DIN-A-MITE Style B Ratings at 100% On

Natural Convection

3-phase, 3-leg 3-phase, 2-leg Single-phase 

Recommended Fuse and Fuse Holder

Fuse

Watlow

Semiconductor

Bussmann

Semiconductor

Watlow

Combination

Bussmann

Combination

20A

17-8020

FWC20A10F

0808-0325-0020

DFJ20

25A

17-8025

FWC25A14F

0808-0325-0025

DFJ25

32A

17-8030

FWP32A14F

0808-0325-0030

DFJ30

40A

17-8040

FWP40A14F

0808-0325-0040

DFJ40

50A

17-8050

FWP50A14F

0808-0325-0050

DFJ50

Holders (single)

Fuse

Watlow

Bussmann

Ferraz

Bussmann

Combination

20A

17-5110

- - - -

USM1i

- - - -

25A

17-5110

- - - -

USM1i

- - - -

32A

17-5114

- - - -

USM141i

- - - -

40A

17-5114

- - - -

USM141i

- - - -

15 to 30A 0808-0326-1530

- - - -

- - - -

CH30J1i

35 to 60A 0808-0326-3560

- - - -

- - - -

CH60J1i

www.

GlobalTestSupply

.com

Find Quality Products Online at:

[email protected]

Summary of Contents for DIN-A-MITE Style B

Page 1: ...nstall electrical equipment This DIN A MITE product is capable of switching up to 40 amps single phase 33 amps 3 phase 2 leg and 22 amps 3 phase 3 leg at 600V ac See the output rating curve in the spe...

Page 2: ...00 of span 4 3 to 19 7mA Temperature stability is less than 0 15 C change Alarm not available on multizone models Shorted SCR Alarm Option Alarm state when the input command signal off and a 10 A or m...

Page 3: ...Table Model Current at 50 C 122 F DB10 35A DB20 DB80 25A DB30 DB90 17A Note Recommended fusing options to meet 200KA SCCR type 1 and 2 approved All other fuse and SCR combinations are defaulted to 5K...

Page 4: ...ins vertically 1 1 2 Mount Dismount Front Allowance for 8 fastener metric M4 Grounding screw 6 Allowance for 8 fastener metric M4 DIN EN 50022 35 mm by 7 5 mm rail clipping distance 34 7 mm 1 366 in t...

Page 5: ...13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac Input 7 8 9 10 11 12 13 Zone 1 V dc Input Zone 2 V dc Input Zone 3 V dc Input 7 8 9 10 11 12 13 14 15 16 1 2 3 4 5 6 Zone 1 V ac Input Zone 2 V ac...

Page 6: ...al injury or death NOTE Use a grounding conductor terminal plate fork terminal having upturned lugs or the equivalent to hold the wire in position Maximum 6 mm2 10 AWG wire Torque Guidelines Properly...

Page 7: ...ountry specific standard wiring practices to install and operate the DIN A MITE Failure to do so may result in damage to equipment and property and or injury or loss of life NOTE If you plan to wire m...

Page 8: ...r each DIN A MITE used Torque Guidelines Properly torque line and load terminals to 1 4 Nm 12 in lb Retorque after 48 hours to minimize wire cold flow Retorque line and load terminals every 3 to 6 mon...

Page 9: ...the alternative latching circuit section below V 13 14 Triac RY1 Coil Reset Switch RY1A L1 L2 RY1B Normally open Common Normally closed External alarm relay contacts set A External alarm relay contac...

Page 10: ...connection NOTES 1 Use of an external filter is required to comply with conducted emissions limits See note 4 below 2 A Line Impedance Stabilization Network LISN was used for conducted emissions measu...

Page 11: ...G All filter installation and wiring must be performed by qualified personnel and conform to local and national electrical codes In line power filters have been shown to properly suppress EMI however...

Page 12: ...n shipment Your P O number Detailed description of the problem Any special instructions Name and phone number of person returning the product 2 Prior approval and an RMA number from the Customer Servi...

Reviews: