D8 Series User’s Guide
Chapter 6: Menu and Parameter Reference
131
Values:
.1 to 999.9 (1 to 9999). Values in parentheses are for communications (values are in tenths).
Default:
1.0 (10) for a thermocouple, RTD or process input.
DeviceNet™ Object:
Ratio (69 hex)
Ratio Set Point Differential
l
01 Ratio SP
r
diff
b
0 ˚C
Enter the value to add to the ratio calculation before using it as the set point.
Values:
-9999 to 9999. Decimal placement depends upon the
Input type
and
Disp format
values in
the
Input
menu.
Default:
0
Decimal Placement for DeviceNet™:
See Decimal Placement for Numeric Values on page 46.
DeviceNet™ Object:
Ratio (69 hex)
I/O Tests Menu
l
I/O tests
r
Other menus
b
Use the
I/O tests
menu to test the following:
• Digital inputs
• Digital outputs
• Keypad
Digital Inputs
l
Digital inputs
r
00000000 1=on
This parameter indicates the states of the eight digital inputs. A
1
indicates that the input is
connected to controller common (on). A
0
indicates an open circuit (off).
To test an input, short it to controller common. When the input is shorted, its input state should be 1.
For detailed instructions, see Digital Input Test on page 31.
The controller display shows the states of digital inputs 1 to 8 from left to right.
Values:
0 if the input is off, 1 if the input is on
DeviceNet™ Object:
Global (6B hex)