Chapter 6: Ramp/Soak
129
Table 6.6
—
Ramp/Soak Profile Modes
CURRENT MODE
AVAILABLE MODE
DESCRIPTION
STRT
RUN
Begin running the assigned profile.
HOLD
CONT
Continue from user-selected hold. The profile runs
from the point when you put the profile in
HOLD
mode. (You cannot continue from a tolerance hold or
a trigger wait.)
After you choose this mode, the controller switches
back to
RUN
mode.
RUN
HOLD
Hold the profile.
Holding a Profile
In
HOLD
mode, all loop parameters stay at their current settings until you change the mode or reset
the profile. To put a profile into
HOLD
mode, follow these steps:
1. In the single loop display, switch to the loop you want to hold.
2. Press the
RAMP/SOAK
key three times to see the
SET MODE
parameter:
ALARM
01 A SEG01/05 R
SET MODE? HOLD
3. Press
YES
to set the mode. While the profile is running, the only mode you will be able select is
HOLD
.
4. Press
ENTER
to hold the profile.
Continuing a Profile
To resume or continue a profile that is holding:
1. In the single loop display, switch to the loop you want to run.
2. Press the
RAMP/SOAK
key three times. The
SET MODE
parameter appears.
3. Press
YES
to set the mode. While the profile is holding, the only mode you will be able select is
CONT
(continue).
4. Press
ENTER
to run the profile.
Responding to a Tolerance Alarm
A tolerance can be set for each segment. The following occurs when the process variable goes
outside this tolerance:
• The profile goes into tolerance hold
• The segment timer holds
• The loop’s single loop display shows
TOHO
• The tolerance alarm timer starts