Name
Description
Read (?) and/or Write (=) Syntax
Range
data.1
data.2
Modbus
Address
Ramping Controller Prompt Table
981,
982,
983, 984
Command Summary Series 981-984, Chapter 5
Data Communications with the Watlow Series 988 Family
5.3
Command Summary Series 981-984 Data Communications
Name
Description
Read (?) and/or Write (=) Syntax
Range
data.1
data.2
Modbus
Address
A2HI
Output 2 Alarm High ? <sp> A2HI <cr>
Process: A2LO to sensor high range
322
= <sp> A2HI <sp> data.2 <cr>
Deviation: 0 to 9999
°
Rate: 0 to 9999
°
/minute
Default: RH, 999
°
, or 999
°
/min.
A2LO
Output 2 Alarm Low ? <sp> A2LO <cr>
Process: sensor low range to A2HI
321
= <sp> A2LO <sp> data.2 <cr>
Deviation: -999 to 0
°
Rate: -999 to 0
°
/minute
Default: RL, -999
°
, or -999
°
/min.
A3HI
Output 3 Alarm High ? <sp> A3HI<cr>
Process: A3LO to sensor high range
341
= <sp> A3HI <sp> data.2 <cr>
Deviation: 0 to 9999
°
Rate: 0 to 9999
°
/minute
Default: RH, 999
°
, or 999
°
/min.
A3LO
Output 3 Alarm Low ? <sp> A3LO <cr>
Process: sensor low range to A3HI
340
= <sp> A3LO <sp> data.2 <cr>
Deviation: -999 to 0
°
Rate: -999 to 0
°
/minute
Default: RL, -999
°
, or -999
°
/min.
ABSP Abort Set Point
? <sp> ABSP <cr>
off
1211
= <sp> ABSP <sp> data.2 <cr>
RL to RH
ACAL Calibration Offset for ? <sp> ACAL <cr>
-999
°
F to 999
°
F
746
Retransmit Output
= <sp> ACAL <sp> data.2 <cr>
-555
°
C to 555
°
C
999 to 999 units
Default: 0
°
F, 0
°
C, or 0 units
AL2
Alarm 2 Type
? <sp> AL2 <cr>
0 = Process Alarm, Input 1
719
= <sp> AL2 <sp> data.2 <cr>
1 = Deviation Alarm, Input 1
2 = Rate Alarm, Input 1
Default: 0
AL3
Alarm 3 Type
? <sp> AL3 <cr>
0 = Process Alarm, Input 1
736
= <sp> AL3 <sp> data.2 <cr>
1 = Deviation Alarm, Input 1
2 = Rate Alarm, Input 1
Default: 0
ALM
Alarm Status
? <sp> ALM <cr>
0 = No alarms occurring (0000 0000)
106
(Writing a 0 clears
= <sp> ALM <sp> 0 <cr>
Bit 1 = A2LO
(0000 0001)
or
next alarm.)
Bit 2 = A2HI
(0000 0010)
110
Bit 3 = A3LO
(0000 0100)
Bit 4 = A3HI
(0000 1000)
106 = Alarm 2
0 = off
1 = HI
2 = LO
110 = Alarm 3
0 = off
1 = HI
2 = LO
AMB
Ambient Terminal
? <sp> AMB <cr>
Input 1 terminals in 0.0
°
F
1500
Temperature
Table 5.3 -
A2HI to AMB
ç
CAUTION:
Avoid writing <=>
continuously, such
as ramping set
points or repetitive
loops, to the
Series 981-984
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to pro-
cesses and
equipment.
NOTE:
The number of
decimal places
returned by many
of these com-
mands is deter-
mined by the DEC1
or IN1 setting.