Watlow Controls 981 Series Calibration Manual Download Page 15

WATLOW Series 988 Calibration Manual

15

mA Process Output

mA Process Output 1 & 2 Procedure

Equipment Required

4 1/2 digit digital multimeter

Setup and Calibration

1. Connect the AC voltage L1, L2 and ground to the proper terminals on the

Series 988.  See Chapter 2 in the user's manual.

2. For Output #1 calibration: Connect the digital multimeter to terminal 

#12 (+) and terminal #14 (-).  Set the DMM to read a range of 0 to 20mA.
Connect the leads of the DMM to measure current. 

For Output #2 calibration: Connect the digital multimeter to terminal 
#15 (+) and terminal #17 (-).  Set the DMM to read a range of 0 to 20mA.
Connect the leads of the DMM to measure current.   

3. Apply power to the unit and let it warm up for 15 minutes.  After warm up put 

the unit in the CAL menu.  See Page 6.

When performing calibration procedures, always do the Output 1 prompts
(beginning with a “1”) first, then continue on to the Output 2 prompts
(beginning with a “2”).  See the Calibration menu on Page 6.

4. At the 1  4 or 2  4 prompt, the multimeter should read approximately 4 mA. Use

the Up or Down keys to adjust the reading on the multimeter for 3.85mA

±

.05mA.   Allow the control to stabilize for 10 seconds.  Press the Mode key to

enter and advance to the next prompt.

5. At the 1 20 or 2  20 prompt, use the Up or Down keys to adjust the reading on

the multimeter for 20.15mA 

±

.05mA.   Allow the control to stabilize for 10 sec-

onds.  Press the Mode key to enter and advance to the next prompt.  To con-
clude the process output calibration, press the Display key.

NOTE:

Any prompt begin-
ning with a “1”
applies to Output 1.
Those beginning
with a “2” apply to
Output 2.

Summary of Contents for 981 Series

Page 1: ...s to Series 981 982 983 984 986 987 988 989 Calibration Manual Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507 W988 CM10 9345 November 1993 5 00 M...

Page 2: ...ion Restore Prompt 7 The dFL Prompt 7 Input Calibration 7 Output Calibration Calibration Procedures 8 Low Gain Thermocouple Input 9 High Gain Thermocouple Input 10 RTD Input 11 mA Process Input 12 VDC...

Page 3: ...control It is explained in detail on Page 4 of this manual In the Calibration menu CAL various input signals must be supplied for the control to go through its auto calibration See Page 5 for the com...

Page 4: ...hotocopies instead diAg Software revision Serial number Ambient temperature Ambient A D count Diagnostics Factory ship date Your Readings DAtE SOFt Sn _ _ AMb Acnt gnd cnt2 itY1 itY2 cnt1 OtY1 OtY2 Ot...

Page 5: ...Universal RTD Curr Heater current Output Types nonE No module rLAB Relay A B SSR1 0 5A SSR rABS Relay A B with suppression SS1S 0 5A SSR with suppression 2rLY Two relays SSr2 2 0A SSR Proc Process SS...

Page 6: ...IES 988 MODE AUTO MAN CAL Calibration A 50 tc A 0H A 20 A 15 A 00 A380 A 0U A20A b 15 b380 A10U b10U b 0U b 4A b 0u Your Settings b100 1 4 1 20 1 0 1 10 2 4 A 4A b20A Default parameters Your Settings...

Page 7: ...pt See Figure 2 on the previous page The upper display shows the prompt default no while the lower display indicates the input signal prompt Each input calibration prompt is preceded by an A or B sign...

Page 8: ...ter warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Input 1 prompts beginning with an A first then continue on to the Input 2 prompts beginning wit...

Page 9: ...llivolt source to the Series 988 Allow at least 10 seconds to stabilize Press the Up key to change the upper display to YES Press the Mode key 5 At the A 00 or B 00 prompt enter 0 00mV from the milliv...

Page 10: ...s to 1 OFF 2 OFF 3 ON NOTE Any prompt begin ning with an A applies to Input 1 Those beginning with a B apply to Input 2 3 Apply power to the unit and let it warm up for 15 minutes After warm up put th...

Page 11: ...om the case and set the Input 2 DIP switches to 1 ON 2 ON 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When performing calibra...

Page 12: ...he Input 2 DIP switches to 1 ON 2 ON 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures alway...

Page 13: ...ontrol from the case and set the Input 2 DIP switches to 1 1 ON 2 OFF 3 ON 3 Apply power to the unit and let it warm up for 15 minutes After warm up put the unit in the CAL menu See Page 6 When perfor...

Page 14: ...bilize Press the Up key to change the upper display to YES Press the Mode key To conclude the slidewire feedback calibration press the Display key Current Transformer Input Procedure Equipment Require...

Page 15: ...nutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Output 1 prompts beginning with a 1 first then continue on to the Output 2 prompts begi...

Page 16: ...nutes After warm up put the unit in the CAL menu See Page 6 When performing calibration procedures always do the Output 1 prompts beginning with a 1 first then continue on to the Output 2 prompts begi...

Page 17: ...ance to the next prompt To conclude the process retransmit output calibration press the Display key VDC Retransmit Output 3 Calibration Equipment Required 4 1 2 digit Digital Multimeter Setup and Cali...

Page 18: ...18 WATLOW Series 988 Calibration Manual...

Page 19: ...Watlow Process Controls Calibration Manual Watlow Controls 1241 Bundy Blvd P O Box 5580 Winona MN 55987 5580 Phone 507 454 5300 Fax 507 452 4507...

Reviews: