7.3.4 Installation on non-metallic pipes using a saddle bracket
There are different types of saddle brackets available on the market that can be applied in pipes of different
diameters. If an installation of this type is required, follow the instructions below.
NOTE: The maximum application diameter for each sensor size could be reduced due to the different height
between the pipe and the valve.
7.3.5 Flowmeter grounding
Assemble the saddle bracket at the point of installation.
Drill the pipe using the sleeve as a centering jig.
The diameter of the hole must be Ø 25±1mm.
Gasket
1” bracket
If the saddle is equipped
with a female thread, fit
the valve using a 1” male
X male nipple, otherwise
set the valve directly on
the saddle bracket.
Use PTFE tape to ensure
the tightness of the thread.
Install the meter following
the normal assembly
instructions.
Fig. 72
Fig. 73
Fig. 74
GROUNDING CONNECTION BOLT
Grounding rod
GROUNDING CONNECTION BOLT
Grounding rod
Fig. 75 Grounding