background image

 

 

           

Installation

-Brine Line and Overflow Connection-

1.  Position brine tank on a smooth, level surface near the softener resin tank. If necessary, the brine tank can be   

     

placed at a higher level than the resin tank, but never at a lower level.

2.  Install one end of 3/8" O.D. by 1/4" I.D. brine line tubing (included with unit) to push lock fitting located on left side  

     

of control valve.

3.  Remove brine tank cover.

4.  Remove cap from brine well.

5.  Insert opposite end of brine line through outer hole in brine tank.

6.  Connect brine line to compression fitting on safety brine valve located inside brine well. Replace brine well cap.

7.  Install 1/2" I.D. drain line tubing (not included) to the overflow fitting on brine tank located just below the brine line.

8.  Run the opposite end of brine tank drain line to a suitable drain.

NOTE:

  The brine tank drain line is gravity flow and must discharge below the overflow fitting.

CAUTION: 

DO NOT “TEE” to the main drain line from control valve.

NOTE:

  The brine overflow is provided as a back-up in the event the safety float shut-off should fail, allowing the  brine  

 

 

tank to overfill. This drain connection would then carry the excess water to the drain and prevent flooding of the    

 

floor. Therefore, no liability will or can be assumed by the manufacturer of the softener should this occur.

-Electrical Connection-

1. Plug the cord from the control valve into a standard 115 volt / 60 Hz receptacle.

NOTE: 

DO NOT plug into an outlet controlled by a wall switch or pull chain that could inadvertently be turned off.

2. For your protection, this unit is equipped with a 3-prong plug and should be plugged into a grounded receptacle is 
    designed only to accept 2-prong plugs, obtain a 3-prong adapter and secure the ground wire to the receptacle plate  

 

    mounting screw.

WARNING: 

DO NOT remove grounding plug!! An improperly grounded unit could cause injury from electrical shock!

-Pressurizing The System-

1. Remove control valve cover or cabinet lid to access control panel. (See Figure 1.)
2. The control valve must be in the Service position! The word SERVICE is imprinted in the notch on the manual 
    regeneration knob. (See Figure 1.) If needed, rotate the manual regeneration knob CLOCKWISE to this position.

WARNING: 

NEVER turn regeneration knob counter clockwise as this will cause damage to the control valve!

3. Slowly rotate the bypass valve to the SERVICE position. The handle will be parallel with the plumbing lines.
4. Open the nearest faucet to evacuate air from plumbing lines.
5. Check for leaks!!!

8

Summary of Contents for AS24P

Page 1: ...Softener Manual Installation Operation Manual Fully Automatic Demand Water Softeners with 2092 Isobar Control Valve...

Page 2: ...Softener Specifications Page 3 Softener Installation Page 5 Softener Capacity Page 10 Installing the Control Valve Page 13...

Page 3: ...ations 3 General Specifications AS24P AS24VP DS24P DS24VP AS32P AS32VP DS32P DS32VP AS48P AS48VP DS48P DS48VP AS64P AS64VP DS64P DS64VP Grains Capacity lbs Salt Per Regeneration 24K 12 19K 6 32K 15 30...

Page 4: ...t water The surfaces of these beads are covered with sodium ions As hard water enters the mineral tank and comes into contact with the resin an ex change of ions takes place as dissolved Calcium and M...

Page 5: ...llation Requirements A level floor position ahead of piping into water heater Unit must be installed at least 10 ahead of the inlet to a water heater to prevent damage due to back up of hot water DO N...

Page 6: ...d All plumbing lines not requiring soft water should be connected upstream of the softener The brine tank drain line is gravity flow and must discharge below the overflow fitting The brine overflow is...

Page 7: ...on the control valve are 3 4 FNPT 1 FNPT for AS96V DS96V units Caution Raised arrows located on the sides of control valve body and bypass valve indicate proper direction of water flow Install inlet...

Page 8: ...ss water to the drain and prevent flooding of the floor Therefore no liability will or can be assumed by the manufacturer of the softener should this occur Electrical Connection 1 Plug the cord from t...

Page 9: ...hart beginning on page 8 that corresponds with the capacity of the softener 4 Select the salt setting to be used and use this section of the capacity chart NOTE Salt settings are pre set at the factor...

Page 10: ...of People with the Compensated Hardness to find the number of tabs to slide When you have determined the number of tabs to slide consult the regeneration frequency chart below to find the actual tab...

Page 11: ...61 75 2 4 6 12 12 12 NOTE All of these charts assume 75 gallons per person per day usage Regeneration Frequency Slide Out TAB NUMBER of Tabs Out 1 2 3 4 5 6 7 8 9 10 11 12 12 6 4 3 2 1 Model Nominal 3...

Page 12: ...2 12 71 80 2 3 6 6 12 12 12 12 81 90 2 4 6 12 12 12 12 91 100 2 4 6 12 12 12 Model Nominal 64 000 Grain Units 64 of People 1 2 3 4 5 6 7 8 9 Salt Setting 30 lbs Regeneration Hardness Range Number of P...

Page 13: ...tal parts per million ppm by four 4 and then add to the grains per gallon gpg of hardness Use this compensated hardness level when programming the regeneration frequency WARNING DO NOT reduce salt set...

Page 14: ...ne tank when sediment appears in the bottom of the salt compartment 7 Always keep the brine tank supplied with good quality salt a type designed for use in water softeners Servicing Instructions Chang...

Page 15: ......

Page 16: ...710 Orange Street Ashland OH 44805 PH 419 289 1500 FAX 419 289 1515 www watersoftinc com...

Reviews: