F-1031, Section 2119
Page 6 of 24
Typical CAFS Flow - Hand Line
Hose Diameter
Tip Size
Foam Type
Water Flow (GPM)
Air Flow (CFM)
Discharge
Pressure (PSI)
Min. Hose Length
1”
1/2”
Wet
20
20
100
35’
1”
3/4”
Wet
30
20
100
35’
1”
3/4
Fluid
15
45
100
35’
1-
1/2”
15/16”
Wet
80
40
100
100’
1-
1/2”
1-
3/8”
Fluid
30
110
100
100’
1-
3/4”
15/16”
Wet
90
50
100
100’
1-
3/4”
1-
3/8”
Fluid
35
130
100
100’
2-
1/2”
15/16”
Wet
120
60
100
150’
2-
1/2”
1-
3/8”
Wet
190
90
100
150’
2-
1/2”
2”
Fluid
50
155
100
150’
Typical CAFS Flow - Portable Master Stream (Fed by One 2-
1/2” Line)
Hose Diameter
Tip Size
Foam Type
Water Flow
(GPM)
Air Flow (CFM)
Discharge
Pressure (PSI)
Min. Hose Length
2-
/1/2”
1-
3/8”
Wet
300
100
140
150’
2-
1/2”
1-
1/2”
Wet
340
120
140
150’
2-
1/2”
1-
3/4”
Wet
380
135
140
150’
2-
1/2”
2”
Wet
400
140
140
150’
Wet Foam: Melted ice cream consistency - Fire Attack
Fluid Foam: Shaving cream consistency - Exposure Protection
A pumper equipped with an Eclipse
ES compressed air
foam unit can be operated in several pumping modes; wa-
ter only, foam solution without compressed air, com-
pressed air foam and compressed air only for support op-
eration such as operating air tools, filling rescue air bags,
etc. It is possible to pump water from one discharge, foam
solution from another discharge while pumping com-
pressed air foam from yet another, or varying foam con-
sistencies (expansion ratios) from different discharges
simultaneously.
NOTE: Monitor compressor instruments during all op-
erations.
Water Pumping Operations
All unit operations begin with pumping water. See the fol-
lowing instruction for details on how to operate and pump
water from your Waterous fire pump:
·
F-1031, Section 2117,
Operation and Maintenance In-
structions for Waterous S100 Series Centrifugal Fire
Pumps
or
·
F-1031, Section 2109.1,
Operation and Maintenance
Instructions for Waterous CX Series Centrifugal Fire
Pumps
For water only operations, the compressor switch should
be in the “OFF” position which disengages the air com-
pressor.
CAUTION
Overheating hazard.
May cause damage to the pump and/or compressor.
Running the unit without adequate water flow can
cause damage to the pump and/or the air compressor
system.
Advantus
Foam Pump Operation (Optional)
Upon power up, the software revision number will be dis-
played. The unit will then display the flow rate.
Because the conductivity measurement for a given per-
centage mix changes with the flow rate, the calibration
data is stored in an array. The array holds entries for the
various parameters at several different flow rates that are
in between flow rates entered in the data array.
Operation
Operator Interface Terminal