Aquis

t

 Foam Pump Operation

Upon power up, the software revision number will be dis­
played. The unit will then display the flow rate.

The software will perform a linear interpolation to determ­
ine values to use for flow rates that are in between flow
rates entered in the data array.

Figure 2. Operator Interface Terminal

IL3437

During normal operation, the OIT (Operation Interface Terminal) will display flow rate, percent mix, total water or total
product.

SELECT

Selects data to display. The default is to display flow rate. Pressing the SELECT button will
scroll through the list, then wrap back around to the top of the list. The associated LED will
light to indicate what data is being displayed.

Flow Rate

Mix Percentage

Total Water

Total Product

Holding the SELECT button for more than two (2) seconds will lock the display to the current
position. Pressing the SELECT button again will unlock.

UP ARROW

When the Mix Percentage is displayed, the current mix setpoint will be displayed. Sub­
sequent presses of the UP ARROW button will increase the Mix Setpoint by 0.1%. After a ten
(10) second timeout, the display will return to the Flow Rate display.

DOWN ARROW

When the Mix Percentage is displayed, the current mix setpoint will be displayed. Sub­
sequent presses of the DOWN ARROW button will decrease the Mix Setpoint by 0.1%. After
a ten (10) second timeout, the display will return to the Flow Rate display.

Pressing both UP and DOWN simultaneously when the Total Water is displayed resets the
Total Water accumulator to Zero.

Pressing both UP and DOWN simultaneously when the Total Product is displayed resets the
Total Product accumulator to Zero.

Pressing both UP and DOWN simultaneously for two (2) seconds, when the Flow Rate is
displayed enters the MANUAL mode of operation. See Manual Mode operation below.

Pressing both UP and DOWN simultaneously while in Mix % will go to the preset default %.

FOAM

Pressing the FOAM button will alternately start and stop the foam operation. When the con­
troller is running, the FOAM LED will be lit. The FOAM LED will blink when the motor control
output is active.

MANUAL MODE

If the display is showing the flow rate and the two ARROW keys are pressed simultaneously,
held for two (2) seconds, the % MIX LED will light and the display will show a default value of
2.0. Use the UP and DOWN arrow keys to increase or decrease this value in steps of 0.5.

NOTE: Pump output is based on a theoretical ratio of foam to water at 50 GPM.

Pressing both ARROW keys again exits the MANUAL mode and stops the pump.

While in manual mode, you can pause the motor by pressing the RED FOAM button (once).
You can increase or decrease the foam percentage at this time. Resume foam flow by press­
ing the RED button once.

Pressing both ARROW keys again exits the MANUAL mode and stops the pump.

NOTE: Motor/Pump Assembly will operate in MANUAL mode whether or not there is a
water flow. If the INJECT/BYPASS valve is in the INJECT position, foam concentrate
will be injected into the system, which will waste foam concentrate.

AUTO RUN

The system is equipped with an AUTO RUN feature. If the voltage (+12 or 24 VDC) is ap­
plied to position 1 on the terminal strip, it will have the same effect as pressing the Red
FOAM button. This will start the Foam system. The system will not inject foam until water is
flowing.

Summary of Contents for Aquis Foam Manager

Page 1: ...ice and Maintenance 6 Maintenance Schedule 6 Location of Maintenance Items 6 Advantus Foam Pump 6 Oil Fill and Drain 6 In line Foam Concentrate Strainer 6 Calibration 7 Aquis Foam Pump 7 Troubleshooting Guide 8 Foam Manager with Advantus Waterous Company 125 Hardman Avenue South South St Paul Minnesota 55075 USA 651 450 5000 Instructions subject to change without notice Visit us at www waterousco ...

Page 2: ... with pump intake or pump discharge connec tions relieve pressure by opening drains or bleeder valves Bleeder valves should also be used while filling a hose connected to an intake with water WARNING Scalding Water Hazard May result in serious burns When operating the pump be sure to open at least one discharge valve slightly to prevent the pump from overheating If the pump runs for a few minutes ...

Page 3: ...he ideal water to concentrate ratio for superior foam Foam Pump The 12 or 24 volt electric motor driven positive displace ment triplex plunger foam pump is equipped with an alu minum crankcase ball bearings forged brass pump body and manifold solid ceramic plungers stainless steel check valves and piston guides Buna packing and preset thermal and pressure relief valves The foam pump is rated at 2 ...

Page 4: ...able Operation A pumper equipped with a Foam Managert foam unit can be operated in water only and or foam modes It is pos sible to pump water from one discharge and foam solution from another discharge Water Only Operations All unit operations begin with pumping water See the fol lowing instruction for details on how to operate and pump water from your Waterous fire pump F 1031 Section 2114 Operat...

Page 5: ...P and DOWN simultaneously when the Total Product is displayed resets the Total Product accumulator to Zero Pressing both UP and DOWN simultaneously for two 2 seconds when the Flow Rate is displayed enters the MANUAL mode of operation See Manual Mode operation below Pressing both UP and DOWN simultaneously while in Mix will go to the preset default FOAM Pressing the FOAM button will alternately sta...

Page 6: ... Flushing System Change Foam Pump Model Level from Top of Oil Fill Port Capacity Required for Oil Change Use Oil Daily or After Each Use Annually Aquis 2 5 1 4 inch 6 mm 90 quarts Total capacity is 1 0 quart Synthetic 10W 30 Mobil 1 recommended Monthly Depending on the corrosiveness of the foam concentrate to be used flushing of the foam injection circuit may be necessary Most Class A foam concen ...

Page 7: ...ill allow for calibration of the water flow in the units of measurement selected D F3 Flow Rate Calibration 1 Press the SELECT button at the F3 prompt The current measured flow rate will be displayed Es tablish a flow using an accurate flow measuring device 2 Once this is established press the UP or DOWN but ton to advance to the calibration step If the displayed flow rate is correct press the SEL...

Page 8: ...dition applies to tanks utilizing a common wall s between the foam tank and the water tank If a leak is confirmed repair the foam tank and flush the water tank and pump until foam is cleared Foam proportioning manifold check valve mal function If the above conditions have been corrected the final cause for foam in the water tank may be the result of a malfunctioning foam manifold check valve To tr...

Reviews: