background image

7

Copyright © 2021, Waterite, Inc.  All Rights Reserved

1.4. Installing the Drain Line

1.  A 1/2” poly tube (minimum) should be used for the hard plumbed drain line. 

2. 

Attach the drain line to the ½” fitting on top of the flush solenoid (Figure 6).

3.  Position the drain line over the drain and secure leaving a 2-3” air gap. Do 

not elevate the drain line over 10 feet above the unit.

4.  If connection to a sewer line is necessary, check the local code or a plumbing 

professional for guidance and the required parts. Drain line should be ¾”.

!

ALWAYS MAINTAIN OR INSTALL A 2” AIR GAP ON ALL DRAIN LINES TO 

PREVENT SEWAGE BACK SIPHONAGE.

DO NOT 

use a residential septic field for receiving the RO waste from VectaMaxx™ RSL systems. If used to capacity, these systems 

(depending on the model and settings) will produce between 1670 to 9820 USG (6,300 to 37,400 litres) per day of wastewater and will 

waterlog septic beds.

1.5. Product Output Connection

1. 

The port at the top of the product flow meter is where the system will connect to the plumbing system for distribution of 

product water. 

2. 

The flow meter connection is equipped with ½” NPT threads, and a ½” push-on fitting.

3. 

Connect the top port of the product flow meter to the distribution system. Be sure to include a check valve to prevent back 

flow from the distribution system. 

If a check valve is not present, the distribution system can back feed the system and 

leak to drain, damaging membrane. (Figure 3)

1.6. Complete the Electrical Connection

1.  Connect 12 ga minimum, 3 wire cable from the control box to an approved electrical breaker or a disconnect switch as per 

local electrical code. 

2.  Connect cable to supply power terminal block in the Control Box as per electrical codes.

3.  Connect Tank Float, or Pressure switch to appropriate terminal (if applicable). See Section 6. Float switch contacts should be 

closed when the tank is empty, and open when the tank is full. Please refer to the instructions provided with the float switch 

for more detail. Note: Switch connections are 

Dry Contact / Voltage Free 

only.

NOTE: 

Local electrical codes vary. Check with an electrician for appropriate device connection in accordance with local codes. Assure 

the power source is rated to the necessary current (see below) and that connections meet the local electrical code. See Section 6 for 

electrical diagram.

230/208VAC 1 PH

230/208VAC 1 PH

RSL2400

8.7/9.4 A

RSLHP2400

15.0/16.5 A

RSL4800

8.7/9.4 A

RSLHP4800

15.0/16.5 A

RSL7200

10.4/11.5 A

RSLHP7200

15.0/16.5 A

RSL9600

10.4/11.5 A

RSLHP9600

15.0/16.5 A

Consult an electrician if supply power is subject to variability. A boost transformer may be necessary especially in rural areas with 208V 

supply. Other motor voltages are available as a factory option. Consult your dealer for availability and pricing.

!

DO NOT START THE SYSTEM UNTIL STEPS 2.4-2.5 ARE COMPLETED.

Figure 7

Summary of Contents for Vectamaxx RSL

Page 1: ...OWNER S MANUAL Vectamaxx RSL and RSLHP Commercial RO Systems Manufactured by WATERITE INC 5 200 Discovery Place Winnipeg MB R2R 0P7 www waterite com...

Page 2: ...intenance 12 3 1 Pre Filter Maintenance 12 3 2 Pre Filter Replacement 12 3 3 Membrane Service Life 12 3 4 Membrane Removal 13 3 5 Membrane Installation 13 3 7 Monitoring System Performance 14 3 8 Auto...

Page 3: ...ll be available during the Pretreat regeneration cycle This will prevent the system from operating periodically with untreated feed water and prolong the life of the filter and membranes How can I get...

Page 4: ...mum water level in the tank make sure that a check valve is installed in the product water line between the RO unit s outlet and the tank inlet This will ensure that backpressure from the tank will no...

Page 5: ...n a location that has access to 230 208VAC power a feed water line a drain capable of handling the waste flow from the machine and close to the storage tank 3 Make sure the feed water source is capabl...

Page 6: ...elements 1 Remove the filter housing by turning counterclockwise with the housing wrench supplied Figure 4 2 Inspect O ring for damage and to make sure it is seated correctly Figure 5 3 Remove plastic...

Page 7: ...e is not present the distribution system can back feed the system and leak to drain damaging membrane Figure 3 1 6 Complete the Electrical Connection 1 Connect 12 ga minimum 3 wire cable from the cont...

Page 8: ...er Programs The controller has 2 separate user selectable settings for configuring the RO The settings are identical except for variations in the membrane flush procedure If your feed water is a munic...

Page 9: ...from the system close the Reject valve Figure 10 until you have a flow rate of 5 GPM Let the system operate for about 5 minutes with Recycle valve fully open 9 The system is now flushing preservative...

Page 10: ...You may wish to lock the valves in the proper position by removing the handles to discourage tampering 5 Your system is now set up to operate at its designed settings RSLHP Units 1 Slowly close the re...

Page 11: ...may do so though this must be accomplished by a combination of increasing the flow of concentrate to waste and reducing the recycle valve flow This done in balance will maintain the overall system pre...

Page 12: ...e 6 Dry thoroughly with clean lint free cloth or compressed air 7 Inspect O ring for damage and verify it is seated correctly Figure 4 8 Remove all plastic wrapping from filter cartridge Insert the ne...

Page 13: ...on membrane housing s Down Flow Membranes 1 Remove plastic wrapping packaging from the membrane element s 2 Lightly lubricate the membrane brine seal and all O rings located in the membrane housing ca...

Page 14: ...power 16 Perform system startup and flush procedure See 2 4 System Startup and Flush Procedure 17 Inspect system for leaks MEMBRANES ARE SHIPPED WITH AN ANTI BACTERIAL PRESERVATIVE OPERATE THE SYSTEM...

Page 15: ...ing power supply automatically adjusts to supply voltage Voltage applied to the input is the same voltage the motor and valves will operate on Relay output ratings Feed solenoid 2A Output Voltage is t...

Page 16: ...Requirements 230 208V 230 208V 230 208V 230 208V 230 208V 230 208V 230 208V 230 208V 6 4 7 1A 6 4 7 1A 10 3 11 3A 10 3 11 3A 10 3 11 3A 10 3 11 3A 10 3 11 3A 10 3 11 3A 120V Option Canada only Yes Ye...

Page 17: ...essure Recycle valve out of adjustment See Step 2 5 Plugged or restricted recycle valve Clean or replace Crimped or damaged product line Repair or replace product line Membranes fouled Clean or replac...

Page 18: ...opyright 2021 Waterite Inc All Rights Reserved SECTION 6 ELECTRICAL INFORMATION Motor Service factor all units Amps x 1 30 ALL RSL AND RSLHP UNITS ARE WIRED 230 208VAC 1 PH 60HZ UNLESS OTHERWISE SPECI...

Page 19: ...19 Copyright 2021 Waterite Inc All Rights Reserved Figure 19...

Page 20: ...off Switch N O FRG22 ALL 4 2 Pressure Gauge 0 100 psi LDU10025 ALL 5 2 Pressure Gauge 0 200 psi LDU20025 RSL 6 2 Pressure Gauge 0 300 psi LDU30025 RSLHP 7 Pre filter Housing Wrench HAN13W ALL 8 Produ...

Page 21: ...21 Copyright 2021 Waterite Inc All Rights Reserved...

Page 22: ...yright 2021 Waterite Inc All Rights Reserved SECTION 8 SYSTEM PERFORMANCE LOG Date Line Pressure System Pressure Permeate TDS Feed Water TDS Pre Filter Change Fast Flush Permeate Flow Meter Waste Flow...

Page 23: ...23 Copyright 2021 Waterite Inc All Rights Reserved THIS PAGE HAS BEEN LEFT INTENTIONALLY BLANK...

Page 24: ...nsibility is limited to any warranty carried by the manufacturer It is the dealer s responsibility to immediately notify Waterite if defects are detected Seller shall not be liable for any special inc...

Reviews: