background image

Installation of Replacement Parts

The Waterite Micronizer consists of a high impact 

Celcon

® 

plastic body containing two water passages. The water passage 

closest to the check valve (2) contains built-in convergent and 

divergent cones forming a venturi. The venturi causes air to be 

drawn into the water stream when water is flowing.

The second water passage acts as a by-pass. The percentage 

of water flow allowed through the by-pass assembly is regulated 

by the valve gate (5) and gate retainer (6) assembly. This in 

turn regulates the amount of air drawn into the water stream 

through the venturi. Turning the valve gate screw clockwise 

forces more water through the venturi passage. This in turn 

causes more air to be drawn into the water stream.  In the 

event that parts must be replaced, this can be accomplished by 

following a few simple instructions:

1.  To replace die rubber check valve (2), wet the check valve 

with 

water ONLY

 and install it in the main body. Thread 

the cap down snugly by hand. 

Do not over tighten. 

Failure to lubricate the rubber properly will cause the valve 

to twist inside the cap and will result in leakage of water 

through the valve. If this should occur, remove the valve, 

relubricate, and install it.

2.  To replace the o-ring or valve gate/ gate retainer assembly, 

start by lubricating the rubber o-ring with water or a silicone 

oil.  Carefully insert the o-ring into its seat in die bottom of 

the hole in the main body. Thread the valve gate fully into 

the gate retainer. Thread the gate retainer into the main 

body by hand to a snug fit. With the use of a suitable tool 

(wrench or pliers), turn the gate retainer another 1/4 turn 

into the main body. 

Do not over tighten.

Note:  To prevent leakage at the 1” NPT threads, use Teflon 

tape during the assembly of the Micronizer to the plumbing 

system. Care should be taken when wrapping the tape over 

the threads to ensure that no tape enters the Micronizer and 

blocks the venturi.

W-988 Micronizer Parts

P/N

1 Knurled Cap, Plastic

WA14051

2 Check Valve M-005

WA14047

3 Main Body – blue M-988

WA14056

4 O-ring M-011

WA14059

5 Valve Gate, Stainless

WA14054

6 Gate Retainer, Stainless

WA14041

  

 Waterite                           ® Model W-988

Installation of your Micronizer in a 

Private Well Water System

1. Start Up Procedure

See  figure  1  below  to  review  a  typical  air  injection  system 

configuration.  The air should first be flushed from the filter tank 

and the filter media conditioned.

a.  Check to verify that die Micronizer Adjusting Screw is in the 

fully open position (turned fully counter-clockwise).

b.  Adjust the pressure switch to ensure a 20-psi differential 

between cut-in and cut-out, (example: 20-40 psi) for the 

pump.

c.  Partially close valve D, turn on the pump, thereby filling the 

pressure  tank  and  slowly  filling  the  filter  tank  until  water 

overflow appears at the backwash.

d.  Fully open valve D and backwash until the water to drain 

appears free of air. Cycle to “Backwash-Rapid-Rinse” 

several times to completely remove the air and orient the 

filter bed, then turn the control handle to “Service”.

2. Adjusting the Micronizer

a.  The  proper  adjustment  of  the  Micronizer  to  provide  a 

colloidal  suspension  of  the  iron  is  a  final  and  important 

step.

b.  Close valve D. Close down the Micronizer Adjusting Screw 

three turns by rotating it clockwise.

c.  Open valve D and open a faucet in house. Then control 

the water flow with valve D. Drain water from the pressure 

tank until the pump starts, then immediately turn off Valve 

D. Using the second hand on a watch, time the pump-

up cycle (i.e. the time from the low pressure cut-in of the 

pump to the high pressure cut-out.) Assume a time of 99 

seconds.

d.  Re-open valve D until the pump starts, then immediately 

shut Valve D. Determine the time of air-draw at the Suction 

Nozzle. This time should be 30% of the total pump-up 

time, (i.e. 30 seconds). If the air draw time is more than 

30 seconds, turn the Adjusting Screw (counterclockwise) 

slightly. If the draw time is less than 30 seconds, turn the 

screw clockwise. Determine the total pump time after each 

adjustment,  since  this  time  will  change  as  the Adjusting 

Screw is being reset.

e.  If all the iron is not being removed at the 30% setting of the 

Adjusting Screw, after 4 weeks, increase the air draw time 

to 35% of the total pump-up time (35 seconds).

Reviews: