TRUCLIMATE 700 90-140 TON INSTALLATION MANUAL
Controls and BAS Integration
Operation and Connection
With a DDC device the chiller may be controlled by a
building management system. The DDC device can work
over several different commination protocols (BACnet
MSTP is standard). DDC devices can be customized to relay
an array of refrigeration, electrical and water information
about the chiller. The User Management interface supports
multiple users wich allows you to assign different levels of
accessibility to different users.
Default (Adjustable) Parameters:
•
Mac Address - 42
•
Protocol - BACnet MSTP
•
Baud Rate - 38400
HydroLink2
10" Touch Interface
Master Panel Connections
If a master panel is present, then the BAS will only connect
to the master panel and will need to run a single shielded
twisted pair cable (22 gauge) to the RS 485 card on the
HydroLink Aurora on one of the chillers. Daisy-chain to
each additional chiller.
BACnet
The BAS will land a single shielded twisted pair cable (22
guage) to the RS 485 card on the HydroLink Aurora. Daisy-
chain if more devices are in series.
Lon Works
The BAS will land a wire pair to the Lon card on the
HydroLink Aurora
Remote Access
An Ethernet cable will need to be ran to the chiller with 1
static IP for remote accessibility.
Individual Chillers
Stand Alone
Unit is controlled by aquastat mode or remote setpoint
through the tablet HMI.
BACnet
The BAS will land a single shielded twisted pair cable (22
gauge) to the RS 485 card on the HydroLink Aurora. Daisy-
chain if more devices are in series.
Remote Access
An Ethernet cable will need to be ran to the chiller with 1
static IP for remote accessibility.
35
10" Touch Interface
15 Amp convenience outlet
HydroLink2
NEMA Control box
Color
touchscreen
tablet
Summary of Contents for TruClimate 700
Page 2: ......
Page 10: ...10 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data...
Page 11: ...11 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Service Clearance...
Page 12: ...12 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Center of Gravity...
Page 13: ...13 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Dimensional Data Rigging Data...
Page 25: ...25 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Wiring Schematic next page...
Page 36: ...36 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Evaporator Pressure Drop...
Page 37: ...37 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Condenser Pressure Drop...
Page 39: ...39 TRUCLIMATE 700 90 140 TON INSTALLATION MANUAL Screw Refrigeration Cycle Analysis...