background image

997-060180-6 

 

4

INSTALLER 

INFORMATION / ADVANCED FEATURES 

 

 

SAFETY CONSIDERATIONS 

Improper wiring or installation may damage thermostat.   Wiring must  
conform to local and national electrical codes 

INTRODUCTION 

The thermostat is a wall mounted, low-voltage thermostat which maintains room 
temperature by controlling the operation of a heating and air conditioning 
system.  Batteries are not required; temperature and mode settings are preserved 
with the power off. 

INSTALLATION CONSIDERATIONS 

The thermostat requires no batteries.  The thermostat is not a power stealing 
device and MUST have both R and C connected. 

 

INSTALLATION 

IV.

 

THERMOSTAT LOCATION 

Thermostat should be mounted: 

- Approximately 5 ft. (1.5m) from floor. 
- Close to or in a frequently used room, preferably on an inside  

partitioning wall. 

- On a section of wall without pipes or duct work. 

Thermostat should NOT be mounted: 

  - Close to a window, on an outside wall, or next to a door leading  

to the outside. 

  - Exposed to direct light and heat from a lamp, sun, fireplace, or  

other temperature-radiating object which may cause a false reading. 

  - Close to or in direct airflow from supply registers and return-air grilles. 
  - In areas with poor air circulation, such as behind a door or in an alcove. 
 

V.

 

INSTALL THERMOSTAT 

1.  Turn off all power to unit.  
2.  If an existing thermostat is being replaced:  

A.  Remove existing thermostat from wall. 
B.  Disconnect wires from existing thermostat, one at a time.  Be  

careful not to allow wires to fall back into the wall. 

C.  As each wire is disconnected, record wire color and terminal marking. 
D.  Discard or recycle old thermostat. 

NOTE:  

Mercury is a hazardous waste and MUST be disposed of properly. 

3.  Separate the front and back pieces of plastic. 

4.  Route thermostat wires through hole in back piece of plastic.  Level plastic 

against wall (for aesthetic value only - thermostat need not be leveled for 
proper operation) and mark wall through 2 mounting holes. 

5.  Drill two 3/16-in. mounting holes in wall where marked.  (Note: Mounting 

holes on thermostat are designed to fit on a horizontal J-box). 

6.  Secure back plastic to wall with 2 anchors and screws provided making sure 

all wires extend through hole in plastic. 

7.  Connect wires to proper terminal of the connector block in the front plastic. 
8.  Push any excess wire back into wall.  Excess wire inside the thermostat 

plastic case can interfere with proper air flow across the temperature sensor.  
Seal hole in wall to prevent air leaks.  Leaks can affect operation. 

9.  Snap front and back pieces of plastic together. 

  10.  Turn on power to the unit. 
 

WIRING DIAGRAMS 

All excess wire should be pushed back into the wall as far as possible.  Excess 
wire inside the thermostat plastic case may interfere with the air flow across the 
temperature sensor.  

THERMOSTAT CONNECTIONS 

 

     

C – 24V Common for Control Circuit 

 

      

R – 24V Supply for Control Circuit 

 

     

W1 – Auxiliary Heat 

 

     

W2 – Not Used 

 

     

H – Humidifier (When used) 

 

     

DH – Dehumidifier (When used) 

               

O – Reversing Valve - energized in COOL mode 

 

2 – 2nd Stage Compressor / Cooling / Heating 

     

Y

  

 

 

 

Y1 – 1st Stage Compressor / Cooling / Heating 

 

     

G – Fan 

 

     

L –

 

Alarm Input 

 

     

V – Not Used 

        

    A+, B – Not Used 

    

  GND – Ground 

      

  OD – Outdoor Temperature Sensor  

 

           

 

ID – Indoor Temperature Sensor 

THERMOSTAT

GEOTHERMAL

C

C

-

DH

R

R

W1

W1

H

O

O

Y2

Y2

Y1

Y

G

G

L

L

-

A+

B-

GND

OD

ID

GND

INDOOR       

SENSOR

TP32U03 & TP32U04 THERMOSTATS ONLY

OUTDOOR       

SENSOR  

 

THERMOSTAT

GEOTHERMAL

C

C

C

C

-

DH

R

R

R

R

W1

W1

W1

H

H

O

O

Y2

Y2

Y2

Y1

Y1

Y1

G

G

L

L

-

A+

DX+

OD

B-

DX-

OD

GND

OD

ID

GND

INDOOR          

SENSOR

TP32U05 THERMOSTAT & DAUGHTER BOARD

OUTDOOR     

SENSOR

DAUGHTER

O

G

L

 

*** Dashed line represents 2 Stage Heat Cool Connections and optional “L”        
terminal connection for Control Board & Comfort Alert faults 

VI. INSTALLER 

SETTINGS 

NOTE:    These options are intended to be used by the installer.  End users are 
not advised to change or modify any of these settings.  Doing so may make 
your equipment stop working properly and/or may void the warranty of the 
thermostat as well as the equipment hooked up to the thermostat.  To access 
the installer setting menu, the mode must be set to OFF.  Then, press both the 
up and down arrows keys at the same time for at least 5 seconds to enter the 
installer screen. 
 
MODEL CONFIGURATION 
 Options to select from: 
PROGRAMMABLE / NONPROGRAMMABLE,  
SINGLE STAGE/MULTI STAGE 

Single Stage

 – Used with heat pumps with PSC motors 

Multi Stage

 – Used with heat pumps with ECM motors, either Single 

Speed or Dual Capacity  

NORMAL/DUAL FUEL/INTELLIZONE STANDARD/ INTELLIZONE NO 
DOWN STAGING 
 

Normal

 – used for normal operation 

 

Dual Fuel

 – used on dual fuel systems Needs outdoor sensor to                             

 

lockout dual fuel. 

Intellizone Standard

 – used with Intellizone.  The ‘W’ acts like a Y3 

and requires less droop.  It activates 3

rd

 stage with the same 

time/temperature weighting as Y1 and Y2. 

Intellizone No Down Staging

 – used with Intellizone and if used, 

SHOULD BE ONLY ON MAIN ZONE.  The thermostat will hold 
the deepest call encountered and should minimize compressor speed 
changes. 

 
ACCESSORIES 
Each of these options has settings for Cumulative Run Time and Calendar 
Time.  Messages will flash at the top of the Main screen when these events are 
met to alert the owner that it is time service these options.   

Reviews: