background image

CHIMNEY TYPES:  USA ONLY

The stove must be connected to a UL listed residen-
tial type HT and Building Heating Appliance chimney
installed in accordance with the manufacturers
instructions or a masonry chimney constructed in
accordance with NFPA211 Chimney Vents and Solid
Fuel Burning Appliances.

CHIMNEY TYPES:  CANADA ONLY

The stove must be connected to an Underwriters
Laboratories of Canada labelled factory built 650

o

C

chimney, installed in accordance with the manufac-
turers instructions or in a lined masonry chimney
acceptable to the Authority having jurisdiction.

CHIMNEY CONNECTOR

The chimney connector is a smoke pipe used to
connect the Waterford Erin 90 T/V & R/V Stove to
the chimney described above.  The chimney con-
nector must be made of Corrosion Resistant Steel,
24 gauge or heavier (Black or Blued or equivalently
treated steel).  Be sure to fasten the chimney con-
nectors together and also to the flue outlet of the
stove through the two holes provided, use at least
two screws for each joint.  Be sure that the joints are
tight and fully secured.

CHIMNEY CONNECTOR USA ONLY

Connectors should maintain a pitch or rise of at least
1/4” to the foot from the stove to the chimney.  It
should be installed so as to avoid sharp turns or
other construction features that would create exces-
sive resistance to the flow of flue gases.  It should be
securely supported with joints fastened with sheet-
metal screws, rivets, or other approved means.  The
entire length of a connector should be readily acces-
sible for inspection, cleaning, and replacement.

The connector may pass through walls or partitions
constructed of combustible materials provided the
connector is either listed for wall pass-through or is
routed through a device listed for wall pass-through
and is installed in accordance with the conditions of
the listing.  Any unexposed metal that is used as part
of a wall pass-through system and is exposed to flue
gases shall be constructed of stainless steel or other
equivalent material that will resist corrosion, soften-
ing, or cracking from flue gas at temperatures up to
982

o

C.

CONNECTING TO MASONRY CHIMNEY

The connector to a masonry chimney must extend
through the wall to the inner face or liner but not
beyond, and must be firmly cemented to masonry.
The connector may pass through walls or partitions
construction of combustible material to a masonry
chimney provided the connector system selected is 

installed in accordance with the proper clearances
and conditions.  (See figs. A,B,C,D page 8)

THIMBLES

Thimbles for chimneys or vent connector should be
of fire clay (ASTM c 315, Specifications for Clay Flue
Linings) galvanised steel of minimum thickness of
24 gauge, or material of equivalent durability.
Thimbles should be installed without damage to the
liner.  The thimble should extend through the wall to,
but not beyond, the inner face of the liner and should
be firmly cemented to masonry.

Thimbles should be located to provide adequate
pitch or rise of chimney or vent connectors and,
where the ceiling above the appliance is constructed
of combustible material, the location of the thimble
should provide minimum clearance required for the
connector as specified in Section under minimum
clearances to combustibles.

Insulation material used as part of wall pass-through
system should be of non-combustible material and
should have a thermal conductivity of 1.0 Btu.in./ft.F
(4.88kg.cal/hr.m.C) or less.  All clearances and thick-
nesses are minimums;  larger clearances and thick-
nesses are acceptable.  Any material used to close
up an opening for the connector should be of non-
combustible material.  A connector to a masonry
chimney, except for system 2 (Under heading
Chimney Connector Systems, Thimbles and
Clearances), shall extend to piece through the wall
pass-through system and the chimney wall to the
inner face of the flue liner, but not beyond.

CHIMNEY CONNECTOR SYSTEMS, THIMBLES,
AND CLEARANCES FROM COMBUSTIBLE
WALLS

1.

Minimum 31/2” thick brick masonry wall 
framed into combustible wall with a min. of 
12” brick separation from clay liner to com
bustibles.  Fire clay liner (ASTM C315 or 
equivalent) min. 5/8” wall thickness, should 
run from outer surface of brick wall to, but not
beyond, the inner surface of chimney flue 
liner and should be firmly cemented in place.

2.

Solid insulated listed factory-built chimney 
length of the same inside diameter as the 
chimney connector and having 1” or more of
insulation with a min. 9” air space between 
the outer wall of the chimney length and 
combustibles.  The inner and end of the 
chimney length shall be flush with the inside
of the masonry chimney flue and shall be 
sealed to the flue and to the brick masonry

7

Summary of Contents for Erin 90 R/V

Page 1: ...uration SAFETY NOTICE Please read this entire manual before you install and use your new room heater Failure to follow instructions may result in property damage bodily injury or even death If this st...

Page 2: ...already done so Remove the loose fitting hob and place on a non abrasive surface d Place the plastic packing on the ground at the back of the stove and lay the stove on its back on top of the packing...

Page 3: ...8 thick or 1 4 thick cov ered with 1 8 sheet metal is required to cover the area under the heater and to extend to at least 18 at the front and 8 to the sides and embers which may fall out from the do...

Page 4: ...be reduced to 91 2 Pipe shield and heat shields are not supplied as standard 4 REDUCED CLEARANCES Under certain conditions the minimum clearances may be reduced by means of a Listed Waterford rear hea...

Page 5: ...GLASS CLIPS 39 LARGE GLASS CLIP 40 TOP COVER PLATE TO DOOR FRAME 41 BOTTOM COVER PLATE TO DOOR FRAME 42 CONTROL KNOB 43 SHAFT 44 SPACER 45 TOP AIR DUCT PLATE 46 SECONDARY AIR BAFFLE 47 SPRING 48 CLAM...

Page 6: ...the bottom and top edges with at least a 1 air gap 4 All clearances shall be measured from the outer surface of the combustible material to the nearest point on the surface of the Erin 90 T V R V disr...

Page 7: ...ust be firmly cemented to masonry The connector may pass through walls or partitions construction of combustible material to a masonry chimney provided the connector system selected is installed in ac...

Page 8: ...enetrate chimney flue liner 4 Solid insulated listed factory built chimney length with an inside diameter 2 larger than the chimney connector and having 1 or more of insulation serving as a pass throu...

Page 9: ...he chimney where necessary Burn directly on hearth do not use a grate or elevate fire Never use gasoline gasoline type lantern fuel kerosene charcoal lighter fluid or smaller liquids to start or fresh...

Page 10: ...ue temperature at the start of a low or overnight burn are too high it will result in reducing burn time 1 Allow the fire bed to cool down 2 Re load using full length wood preferably unsplit 3 Do not...

Page 11: ...fully b Remove the four corner screws and clips items 38 39 and carefully remove the broken glass c Clean the glass recess in the door d Attach adhesive thermal tape to the perimeter of the replacemen...

Page 12: ...her to contend with small fires resulting from burning embers 5 A practical evacuation plan 6 A plan to deal with a chimney fire as follows In the event of a chimney fire a Notify the fire department...

Reviews: