background image

Emerald Gas Insert Zero Clearance Kit

15

Dia. 4

Dia. 5

Note: If installing termination on a siding covered wall, a

vinyl siding standoff or furring strips must be used to
ensure that the termination is not recessed into the
siding.

7)

Before connecting the horizontal run of vent pipe to the
vent termination, slide the Wall Thimble (Part # 620-926)
over the vent pipe.

8)

Slide the appliance and vent assembly towards the wall
carefully inserting the vent pipe into the vent cap assem-
bly. It is important that the vent pipe extends into the vent
cap sufficient distance so as to result in a minimum pipe
overlap of 1-1/4 inches. Secure the connection between
the vent pipe and the vent cap by attaching the two sheet
metal strips extending from the vent cap assembly into
the outer wall of the vent pipe. Use the two sheet metal
screws provided to connect the strips to the pipe section.
See Dia. 4.

9)

Install wall thimble in the center of the 10" square and
attach with wood screws (Dia 5).

VERTICAL TERMINATION

1)

Maintain the 1-1/2" clearances (air spaces) to combus-
tibles when passing through ceilings, walls, roofs, en-
closures, attic rafter, or other nearby combustible surfac-
es. Do not pack air spaces with insulation. Check page
13 for the maximum vertical rise of the venting system.

2)

Set the gas appliance in its desired location. Drop a
plumb bob down from the ceiling to the position of the
appliance flue exit, and mark the location where the vent
will penetrate the ceiling. Drill a small hole at his point.
Next, drop a plumb bob from the roof to the hole previously
drilled in the ceiling, and mark the spot where the vent will
penetrate the roof. Determine if ceiling joists, roof rafters
or other framing will obstruct the venting system.

INSTALLATION

Summary of Contents for E61

Page 1: ...additional information con sult an authorized installer service agency or the gas supplier FORYOURSAFETY Donotstoreorusegasolineorother flammable vapours and liquids in the vicinity of this or any oth...

Page 2: ...rancestoCombustibles 4 Safety Decal 5 Framing 6 Zero Clearance Kit Assembly 6 Assemble the Cabinet 7 Attach Cabinet to Framing 10 Install the Insert 11 VentingIntroduction 11 SimpsonDura VentComponent...

Page 3: ...the required venting The insert can be installed later The faceplate will normally overlap on top of the finished wall LISTINGS AND CODE APPROVALS This gas component has been tested in accordance wit...

Page 4: ...e g wood metal concrete INSTALLATION Emerald Insert Clearances to Combustibles From Unit Sides A 12 305 mm Unit to Unprotected Mantel B 16 406 mm see Mantel clearance diagram below Unit to Protected...

Page 5: ...E61ZeroClear ance Kit 270 900 We have printed a copy of the contents here for your re view The safety label is located on the top panel NOTE Waterford units are constantly being improved Check the lab...

Page 6: ...tor J Clearance to service regulator vent outlet Canada min 72 1 8m USA min 36 90cm K Clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 12 30c...

Page 7: ...ions given are from the inside of the finished surfaces The ceiling inside the framed enclosure should be a minimum of 55 1 2 1410mm from the base of the plinth 3 For exterior walls use a vapour barri...

Page 8: ...and Base sections upright Slide the Lower Back the section with 4 holes down the inside of Side flanges make sure the 4 holes are closest to the floor see photo Secure with 2 screws on each side and 1...

Page 9: ...pipe over the small vent opening on the base of the adaptor box and secure with a clamp Repeat for the 2nd flex vent pipe Use silicone to seal the connection Left and Right Standoffs in position and...

Page 10: ...ody Secure the Left and Right Panels to the top with 1 screw each Make sure that the outside edges are aligned Fit the assembled Side Top Face Panels to the front of the cabinet and secure with 19 scr...

Page 11: ...other hole Warning Combustiblematerialsmustnotextendinsidethe stand offs on the side top and rear supports For safety reasons do not modify or alter any components of the Kit Any non combustible facin...

Page 12: ...er appliance These venting systems in combination with the E61 Insert and the E61 Zero Clearance Kit 230 900 have been tested and listed as a direct vent heater system by Warnock Hersey The location o...

Page 13: ...outer diameter A vent guard should be used whenever the termination is lower than the specified minimum or as per local codes Maintain a 1 1 4 clearance to combustibles 1 1 2 withFlex Firestopsarereq...

Page 14: ...ons completely togeth er then twist lock one section clockwise approximately one quarter turn until the two sections are fully locked The female locking lugs will not be visible from the outside on th...

Page 15: ...all of the vent pipe Use the two sheet metal screws provided to connect the strips to the pipe section See Dia 4 9 Install wall thimble in the center of the 10 square and attach with wood screws Dia 5...

Page 16: ...Printed in Canada...

Reviews: