Page 22
WS1HR & WS1.25HR Manual
Table 9
Filter Setting Options
Gallons
Capacity
Regeneration
Time Option
Day
Override
Result
oFF
NORMAL
Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the specifi ed
number of days between regenerations is reached.
Any
number
NORMAL
oFF
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when gallons capacity
reaches 0.
Any
number
NORMAL
Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when gallons capacity
reaches 0 or the specifi ed number of days between regenerations is
reached.
Any
number
On O
oFF
Reserve capacity not automatically estimated.
Regeneration occurs immediately when gallons capacity reaches 0.
Time of regeneration will not be allowed to be set because regeneration
will always occur on 0.
Any
number
NORMAL on 0
Any
number
Reserve capacity not automatically estimated.
Regeneration occurs at the next Regen Set Time when the specifi ed
number of days between regenerations is reached or regeneration occurs
immediately after 10 minutes of no water usage when gallon capacity
reaches 0.
Summary of Contents for WS1.25HR
Page 2: ......
Page 13: ...WS1HR WS1 25HR Manual Page 13 Figure 3 Figure 4 Figure 1 Figure 2...
Page 30: ...Page 30 WS1HR WS1 25HR Manual Drawings and Part Numbers...
Page 42: ...Page 42 WS1HR WS1 25HR Manual Flow Diagrams Service and Backwash...
Page 43: ...WS1HR WS1 25HR Manual Page 43 Flow Diagrams Downflow and Upflow WS1HR Only...
Page 44: ...Page 44 WS1HR WS1 25HR Manual Flow Diagrams Rinse and Fill...
Page 54: ...Page 54 WS1HR WS1 25HR Manual...
Page 55: ...WS1HR WS1 25HR Manual Page 55...
Page 56: ...Page 56 WS1HR WS1 25HR Manual...
Page 57: ...WS1HR WS1 25HR Manual Page 57...
Page 58: ...Page 58 WS1HR WS1 25HR Manual...
Page 59: ...WS1HR WS1 25HR Manual Page 59...