Cool Temperature Limit Range – This feature adjusts

 

the lowest setpoint temperature for cool . The default 

 

setting is 45°F . It can be changed between 46°F and

 

82°F by pressing the   or   key . The "

temperature

 

limit" icon will be displayed to the left of your setpoint

 

temperature when using this feature . The "

temperature 

 

limit" icon will flash if an attempt is made to adjust the

 

temperature beyond the range selected .

22) 

Keypad Lockout – This step allows you to select the

 

type of lockout or limited range security required . If no

 

lockout or limited range security is required, press 

 to

 

advance the menu .

 

Three security settings are available in this menu item .

 

Use the   or   keys to select the lockout desired .

 

Lockout selections are:

 

"

Keypad Lockout and L" = Total Lockout . Total Lockout

 

locks all keys .

 

"

Keypad Lockout and P" = Partial Lockout . Partial Lock-

 

out allows only the 

 or 

 keys to operate within your

 

set temperature limits .

 

"

Temperature Limit/Keypad Lockout" prevents

 

changing the temperature limits in the Configuration

 

Menu .

 

Keypad Lockout Combination Number Selection

 

Display will read "

OFF" "Keypad Lockout" .

 

Skip this step and continue through the configuration

 

menu items 19 thru 22 if you require an Air Filter Change

 

out indicator or Humidifier Pad Change out indicator by

 

pressing the 

 button to advance .

 

Return to this point when you are ready to start your

 

selected lock-out and continue by:

 

Pressing   or   keys to select ON .

 

Press 

 . Display will read "

000" .

 

Pressing   or   keys to select your keypad lockout

 

combination number . Note: "

000" is not a valid

 

combination choice .

 

Record the number you select for future use.

 

Press 

 to exit the menu . The security feature you

 

select will start in 10 seconds . The system button will

 

remain active for 10 seconds to allow setting Heat, Off,

 

Cool or Auto .

23 & 24) 

Select Fast Second Stage ON or OFF – In the run

 

mode, with the fast Heat feature enabled (FA Heat On), if

 

the Heat setpoint temperature is manually raised by 3°F

 

 INSTALLER/CONFIGURATION MENU

 

(2°C) or more above the actual temperature using 

 the

 

second stage will energize immediately . With FA OFF, 

 

second stage will not energize until the setpoint tempera-
ture is 1°F or more above actual temperature for more 

 

than ten minutes . The Fast Cool feature (FA Cool) 

 

provides the same controls when the setpoint tempera-
ture is lowered .

25) 

Select Remote Temperature Sensor – This control 

 

allows one wired remote temperature sensor (indoor, 

 

F145-1328, or outdoor, F145-1378) be connected to it

 

and indicates the measured temperature in clock digits . 

 

This menu enables you to select the remote sensor and 

 

also configure it as indoor or outdoor temperature sensor . 

 

Factory default is off . Select 

Remote On and Remote in 

 

(for indoor) or 

Outdoor Remote .

 

Local Temperature Sensor disable – This is applicable

 

only when indoor remote temperature sensor is enabled .

 

Factory default is 

On LS . You can make it Off LS if you

 

desire by using   or   touch keys . Then, only the

 

indoor remote temperature reading will be used for

 

control .

26) 

Select Dual Fuel Feature and Setpoint – This feature is

 

applicable only in heat pump modes . An outside remote

 

sensor must also be installed . When the outside tem-

 

perature falls below the selected setpoint temperature,

 

dF, the thermostat will switch to gas heat and shut down

 

the compressor . Use the   or   keys to select the

 

desired setpoint temperature in the range of 5 to 50 .

 

Factory default is 5, which disables this feature . See

 

Dual Fuel Temperature and Setpoint in Programming

 

section .

 

Select Compressor Delay – When dF is enabled, the

 

shut down of the compressor(s) is delayed for a time

 

period after the auxiliary stage is energized . This delay,

 

Cd, is factory set at 60, but can be set in the range of 0

 

to 99 .

27) 

Select Change Filter Run Time – The thermostat

 

will display "

Change Filter" after a set time of blower 

 

operation . This is a reminder to change or clean your air 

 

filter . This time can be set from 25 to 1975 hours in 25 

 

hour increments . A selection of OFF will cancel this

 

feature . When "

Change Filter" is displayed, you can

 

clear it by pressing Clean Display . In a typical application, 

 

200 hours of run time is approximately 30 days .

Summary of Contents for TP32W03

Page 1: ...at contains mercury Mercury and products containing mercury must not be discarded in household trash Do not touch any spilled mercury Wearing non absorbent gloves clean up any spilled mercury and plac...

Page 2: ...thermostat one at a time Do not let wires fall back into the wall Installing New Thermostat 1 Pull the thermostat body off the thermostat base Forcing or prying on the thermostat will cause damage to...

Page 3: ...C W E Jumper G C W2 Jumper No Output 1st Stage Heat Cool Com pressor Blower Circula tor Fan Energiz ed on call for Heat or Cool 24 VAC Hot Cool DC supply voltage to re mote Temp erature Sensor Remote...

Page 4: ...e 12 Call For Service indicates a fault in the heating cooling system It does not indicate a fault in the thermostat Programming and Configuration Items Figure 3 Programming Configuration Items 13 Sys...

Page 5: ...I Selects Backlight Intensity 13 13 11 0 4 LO to 4 HI Selects Adjustable Ambient Temperature Display range 4 LO to 4 HI 14 14 12 F C Selects F C Display temperature units in Fahrenheit or Celsius 15 1...

Page 6: ...and 98 F by pressing the or key The temperature limit icon will be displayed to the left of your setpoint temperature when using this feature The temperature limit icon will flash if an attempt is mad...

Page 7: ...IGURATION MENU 2 C or more above the actual temperature using the second stage will energize immediately With FA OFF second stage will not energize until the setpoint tempera ture is 1 F or more above...

Page 8: ...ure setting for a default four hour over ride period The override period can be shortened by pressing or lengthened by pressing Program Override period can range from 15 minutes to 7 days Example If y...

Page 9: ...n the fan on for 10 minutes and off for 20 minutes to improve indoor air quality If the display shows FAN On Prog to indicate the program period has the fan programmed to run FAN Prog will override th...

Page 10: ...th the times and temperatures you want Keep the following guidelines in mind when planning your program In Heating lower temperatures will save energy In Cooling higher temperatures will save energy I...

Page 11: ...or is fixed In normal operation of the thermostat the current tempera ture displayed will be the weighted average of the local sensor and the remote sensor using the formula local sensor weight x loca...

Page 12: ...at to COOL and lower the setpoint below the room temperature There may be up to a five minute delay before the thermostat clicks in Cooling Heat Cool or Fan Runs Constantly 1 Possible short in wiring...

Reviews: