WatchGas BEACON SOUNDER User Manual Download Page 8

BEACON SOUNDER

detection

watch

gas

8

4. GENERAL SPECIFICATIONS

DIMENSIONS

92 x 88 mm (3.6 x 3.5”) Dia x H

WEIGHT

250 g (8.82 oz)

MOUNTING

4x M4x35 bolts

COLORS

RGB LED, Red, Yellow, Green and Blue flashing patterns

SOUND

4 types of alarm sounds

SOUND PRESSURE LEVEL

107 dB @ 1 meter (3.3 ft)

POWER SUPPLY

9-30V DC (min. 4W)

STANDBY CURRENT

Max. 10 mA

TRIGGER VOLTAGE POSITIVE

6-30V DC

TRIGGER CURRENT

Max. 6 mA

CABLE DIAMETER

Max. 1,3 mm

2

 Stranded core

5. SERIAL PROTOCOL SPECIFICATION

Specification rev 1.0

INTRODUCTION

This document describes how to control and connect the Beacon Sounder PN: Air-Be-

ac-010 over a serial interface. This serial interface can be used to select colour, display 

effect and sound effect. If the serial input is used, the digital I/O inputs are no longer 

enabled. The document contains source code that can be used as an example of how to 

send commands to the Beacon Sounder.

CONNECTIONS
WIRING

The Beacon Sounder can be powered by 

only one

 of these options:

1.  Use terminal J4 connect 9 – 30VDC (min 10W) to the + and – terminals

2.  Use terminal J2 to connect a 5VDC (+/- 0.1V) 2A power supply. This input has no pro-

tection against overvoltage or supply reversal. Use at your own risk.

J2 PINOUT

PIN

CONNECTION

1

+ 5VDC Power supply

2

TX Signal

3

Do not use

4

GND

NOTE

Cable length of TX signal may not exceed 500mm wire distance form signal source.

The signal voltage should be 3.3V TTL/CMOS.

CONNECTOR & CRIMP

DESCRIPTION

PART NUMBER

MANUFACTURER

WIRE-TO-BOARD RECEPTACLE

22-01-2045

Molex

CRIMP CONTACT GOLD PLATED

08-55-0111

Molex

DIPSWITCH SETTING

Set DIP switch FN 3 to “ON” to configure the Beacon Sounder to use a serial input.

DIP SWITCH 3 FN

Function

ON = J2 TTL Communication protocol

OFF = J4 terminal block input 

PROTOCOL
SPECIFICATION FOR COMMUNICATION

ITEM

VALUE

BAUD RATE

9600 8N1

FLOW CONTROL

None

SIGNALING VOLTAGE

3.3

DocuSign Envelope ID: AD1219C0-C292-4C55-B2EE-1190F300B975

Summary of Contents for BEACON SOUNDER

Page 1: ...USER MANUAL BEACON SOUNDER we watch gas where you can t DocuSign Envelope ID AD1219C0 C292 4C55 B2EE 1190F300B975...

Page 2: ...L 3 1 PRODUCT OVERVIEW 4 1 1 PCB Layout 4 1 2 Drilling Template 4 2 DIP SWITCH SETTINGS 5 3 MOUNTING INSTRUCTIONS 7 4 GENERAL SPECIFICATION 8 5 SERIAL PROTOCOL SPECIFICATION 8 6 LIMITED WARRANTY 13 Do...

Page 3: ...le internal electronical components whilst wiring up Environmental ex posure during installation should be under dry circumstances avoid heavy moist and wet conditions The Beacon Sounder is only weath...

Page 4: ...m2 Stranded core 1 1 PCB LAYOUT 1 Sounder 2 10 pin DIP switch 3 6 pin DIP switch J2 Communication input J4 Terminal block 7 pins Supply Ground BU Blue light GN Green light YL Yellow light RD Red light...

Page 5: ...3 4 3 4 looping 3 4 flashing 10 Hz 50 duty cycle 3 4 DIP SWITCH 5 6 YELLOW LIGHT continuous fancy loop 5 6 5 6 looping 5 6 flashing 10 Hz 50 duty cycle 5 6 DIP SWITCH 7 8 GREEN LIGHT continuous fancy...

Page 6: ...r OFF Falling trigger DIP SWITCH 3 FN Function ON J2 TTL Communication protocol OFF J4 terminal block input DIP SWITCH 4 VOL Volume ON High OFF Low DIP SWITCH 5 BL WH Swap blue to white ON Active OFF...

Page 7: ...ight Ensure all rubber gaskets are placed correctly Insert Supply signal cable through the 5 5mm hole see drilling template Connect supply signal cable to the terminal block Transparent lens O ring le...

Page 8: ...Sounder PN Air Be ac 010 over a serial interface This serial interface can be used to select colour display effect and sound effect If the serial input is used the digital I O inputs are no longer en...

Page 9: ...PTACLE 22 01 2045 Molex CRIMP CONTACT GOLD PLATED 08 55 0111 Molex DIPSWITCH SETTING Set DIP switch FN 3 to ON to configure the Beacon Sounder to use a serial input DIP SWITCH 3 FN Function ON J2 TTL...

Page 10: ...II Hex Green 4 ASCII Hex Blue 5 ASCII Hex Sound mode 6 ASCII Hex CRC All ASCII Hex values are a single value ranging from 0 to F NOTE This command has to be repeated at least every 15 seconds If no co...

Page 11: ...w low Continuously on 4 Alternating low high beeps low Low power rotation effect 5 Continuous 50Hz low Flashing 2Hz 10 duty 6 Reserved Reserved 7 Reserved Reserved 8 Disabled Reserved 9 Continuous 270...

Page 12: ...oHex r 4 cmd 3 toHex g 4 cmd 4 toHex b 4 cmd 5 toHex s cmd 6 toHex cmd 0 cmd 1 cmd 2 cmd 3 cmd 4 cmd 5 0xF cmd 7 r cmd 8 0 Transmit printf const char cmd char toHex uint8_t x if x 10 return 0 x else i...

Page 13: ...lightening water damage or other hazard voids liability of the manufacturer In the event that a product should fail to perform up to manufacturer specifications during the applicable warranty period p...

Reviews: