3.6 Time control regeneration setup
13
STEP 1
- Press
and
simultaneously
for 3 seconds.
STEP 2
– Day Override: When volume capacity is
set to oFF, sets the number of days between
regenerations. When volume capacity is set to
AUTO or to a number, sets the maximum number of
days between regenerations. If value set to oFF,
regeneration initiation is based solely on volume
used. If value is set as a number (allowable range
from 1 to 28) a regeneration initiation will be called
for on that day even if sufficient volume of water
were not used to call for a regeneration. Set Day
Override using
or
:
•number of days between regeneration (1 to 28); or
•oFF.
See Setting Options Table for more detail on setup.
Press
to go to step 3. Press
to return
to previous step.
STEP 3
– Next Regeneration Time (hour): Set the
hour of day for regeneration using
or
.
buttons. The default time is 2:00. This display will
show “
on 0 m3” if “on 0” is selected in Set
Regeneration Time Option in Watch
Proxima
System Setup. Press
to go to step 4 Press
.
to return to previous step.