6-16-19, JINGUMAE, SHIBUYA-KU, TOKYO 150-0001, JAPAN
TEL: +81-3-3400-6147 FAX: +81-3-3409-3156
2/3
IM0874
-
00
5. Circuit Configuration
6. How to Mount
It's possible to install close adherence, but recommended so
that 6.5 mm-more than 7 mm may be opened for thermal
radiation.
It will be 6.5mm between the case body by the 29.5mm space.
.
7. How to Connect to/Disconnect from
DIN Rail
1) How to secure the socket
Engage the hook on the rear upper
side of the socket with the rail with
the slider on the bottom side of the
socket downward, and press the
lower side of the socket in the arrow
direction as shown in the drawing to
secure the socket.
2) How to secure the main unit to
the socket
Position the main unit so that the
characters in the front label can be
read in the appropriate direction,
press the main unit into the socket,
and screw the main unit to secure it.
3) How to disconnect the main unit
from the socket
Loosen the screws that secure the
main unit, and pull the unit out in a
straight line.
4
) How to disconnect the socket
Put a flat head screwdriver into
the slider slot of the socket and
pull the lower side of the socket
in the arrow direction
②
while
pulling the screwdriver in the
arrow direction
①
.
8. How to Connect
Terminal
No.
Sign
Description
1
INPUT
+
These terminals receive the
specified input signals.
4
-
5
NC
No connection
8
NC
No connection
9
OUTPUT1
+
Signals are provided in accordance
with the input/output specifications.
12
-
13
POWER
U(+)
Connect the rated voltage power
supply.
14
V(-)
* No line shall be connected to NC.
9. How to Adjust Output
We have already performed output adjustment in
accordance with your requests at your order. Therefore, no
output adjustment is required if you operate this product
within your requested specifications. If matching with devices
to be connected or regular calibration is required, follow the
steps below.
For calibration, use signal sources (including a standard
voltage/current generator) and measuring instruments
(including a voltmeter and an ammeter) the tolerances of both
of which are more than 10 times that of this product and wait
for 30 minutes or more after turning on the power.
Output adjustment is performed with the setting switch on
the front side of this product.
*
Please don't change a setting condition
(right side) of the selection switch 3 after shipping.
○
How to adjust
①
Set the selection switch 1 (SW SET) to ON.
This action enables switch operation.
②
Set the selection switch 2 (M OUT) to OFF.
③
Set the selection switch 4 (ZS SEL) to ZERO.
Use the UP or DOWN switch to adjust the output to 0%
when a 0%-equivalent input is provided.
④
Set the selection switch 4 (ZS SEL) to SPAN.
Use the UP or DOWN switch to adjust the output to 100%
when a 100%-equivalent input is provided.
1:Switch
Enabled/Disabled
2:Simulated output/
Output adjustment
3:Unused*
4:Zero adjustment/
Span adjustment