background image

 
 
 

(1)The application of voltage or current exceeding its maximum 

allowable value to the input terminals may result in instrument 
damage. 

(2)The supply of power out of its allowable range may cause fire, 

electric shock or instrument failure. 

(3)The content of this manual may subject to change without prior 

notice for product improvement. 

(4)This manual is carefully prepared. However, if any question  

arises, or any mistake, omission or suggestion is found in the 
content of this manual, contact your nearest our sales agent. 

 

2.3. Terminals

 

 
 
 
 
 
 
 
 
 
 
 

2.4. Connection examples

 

 
 
 
 
 
 
 
 
 
 
 
 

1.Outline 

The Model AL-512 digital panel meter is a process monitor which 
has an extremely thin 3-1/2 digit LED display unit and also does 
not require a power supply (driven by a 4 to 20mA signal). 
It is provided with the display having a maximum of 1999 and the 
scaling function by which the input signal can be converted to any 
process variable for its display. In addition, wiring can be easily 
conducted by the use of a screw terminal board. 

 

2.Before operation 

 2.1. Accessory check 

The following accessories are attached to one Model AL-512 digital 
panel meter. 

  Instruction manual  One copy 
  Screw terminal cover  1 pc. 
  If any question may arise on these accessories, please contact your 

nearest Watanabe sales agent or Watanabe directly 

 2.2. Mounting 
 2.2.1. Panel cutout dimensions 
  Prior to mounting the meter, make the cutout through the panel as 

shown in the following figure. 

 
 
 
 
 
 
 
 
 
 
                   Panel cutout dimensions 
 2.2.2. Mounting 
  For mounting the meter, insert it in the panel cutout from the front 

of the panel while pushing the hooks on both sides of the case in 
the case. (See the following figure.) 

 
 
 
 
 
 

Mounting diagram 

 
 
                          
*The Model AL-512 meter produces a voltage drop of about 5.3V  

(at an input of 20mA). 

For this reason, conduct wiring in consideration of the impedance 
in the entire circuit. 

*If this meter is used at a noisy location, ground the E (earth) 

terminal. 

 

3. Functions 

 3.1. Scaling adjustment 

First, remove the front panel of this meter by referring to the 
following figure. Then, turn the Offset adjuster (see the following 
figure) until the desired value is displayed (setting range: ±
200) with an input signal of 4mA applied to the input terminals 
on the meter. 

 Next, turn the Fullscale adjuster (see the following figure) until 
the desired value is displayed (setting range: 100 to 1999) with an 
input signal of 20mA applied to the input terminals. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
*Prior to conducting scaling adjustment, allow more than 20 minutes 

for the meter to warm up. 

 

INSTRUCTION MANUAL 

DIGITAL PANEL METER 

Caution 

MODEL AL-512 SERIES 

WATANABE ELECTRIC INDUSTRY CO., LTD.