Wärtsilä JOVYTEC PMS 2002K / 3002K BAX 4837E
- 21 -
7.3
Configuration
Use of the function display and the function keys allows diverse settings to be made on the UPS unit. The
formalism is as follows:
-
In order to enter the configuration mode press the key
FUNC
for 2 seconds. The first configuration
parameter appears in the display.
-
The key
FUNC
is for navigation through the parameters.
-
The key
ENTER
is used to select the parameter point to be changed.
-
The key
FUNC
is used to navigate through the options of the chosen parameter.
-
The key
ENTER
is used to confirm the selected option. Display will show than:
Save ?
-
Saving is achieved by pressing the key
ENTER
again.
7.4
Table of the adjustable parameters
Adjustable
parameter
Indication in
the display
Explanation
Selections
for
parameter
Factory
setting
Adjusting the output voltage
O/P V adjustment
Nominal voltage
208/220/
230/240V
230V
Setting the
input frequency tolerance
I/P Freq. Adjustment
Frequency tolerance in
unsynchronised mode
± 2%
± 5%
± 7%
± 5%
Setting of the tolerance of the bypass
voltage
I/P bypass adjustment
Voltage tolerance
± 10%
+10/-15%
+15/-20%
+10/-15%
Free Run Mode
Free-Run-Set
Unsynchronised mode
ON/OFF
ON
Bypass activation/deactivation in Free
Run Mode
Free–Run-Mode
If activated the UPS will switch
to bypass if the preset
parameters are not maintained
ON/OFF
OFF
Operating mode setting
HE mode setting
Online/Offline mode
ON/OFF
OFF
Setting for a permanent manual bypass Man. bypass setting
Activate manual bypass (only
for servicing)*
ON/OFF
OFF
Load management
Load segment setting
Segment 1 ON/OFF
Segment 2 ON/OFF
ON/OFF
ON
Performing a battery test
Manual battery test
Battery test
Battery OK.
Battery not OK.
ON/OFF
OFF
Quiet functioning
Alarm acoustic
Activate, deactivate the
acoustic alarm
ON/OFF
OFF
Number of battery packs
No. of ext. batteries
Setting number of battery
packs for the autonomy
calculation; a maximum of 2
1 - 3
Dependent on
the required
backup time
Reversal polarity protection
Phase reversal setting
Activation, deactivation
of phase reversal
ON/OFF
OFF
Language selection
Language
Language selection
English
German
French
Spanish
Italian
German
Generator mode
Generator
Generator mode**
ON/OFF
OFF
Setting RS 232 interface
COM control command Setting of RS232 interface
ON/OFF
ON
*) The manual bypass function should always be switched off since for a switched on manual bypass the load in the case of a
power failure cannot be supplied by the UPS.
**) The UPS should we switched off and then switched on again before the generator is switched.
P L E A S E N OT E!
If the selected option is not stored within 10 seconds then the value is reset
automatically and the menu returns into its normal condition.