NAMSRK INSTALLATION INSTRUCTIONS 
FOR PIPE FREEZE PROTECTION

GENERAL

GFI CIRCUIT PROTECTION 

- To minimize danger from possible sustained electrical arcing due to damaged or improperly 

installed heating cable, and to comply with agency certifications and the National Electric  Code  (Article  427)  -  Ground  Fault  
Equipment  Protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit 
protection. Contact a qualified electrician for installation if GFI is not available.

WARNING: 
ELECTRIC SHOCK AND/OR FIRE HAZARD

. If cable is damaged, remove from service. Do not attempt to repair. There are no user 

serviceable parts. Replace damaged cable with new assembly.

KEEP INSTRUCTIONS FOR FUTURE REFERENCE.

IMPORTANT NOTES ON CABLE SELECTION

• 

For any “non-Standard” installations please contact Warmup at (888) 927-6333 (US) or (888) 592-7687 (Canada).

• 

We assume a minimum ambient temperature of 0°F and a thermal insulation of thick fiberglass wrap or equivalent.  
For   protection   to   -20°F   minimum   ambient   use   1”  thick fiberglass wrap or equivalent.

• 

Add 1 foot of heating cable for every valve or spigot in the pipeline - make sure to apply this extra cable at each valve/
spigot when installing.

• 

If your selected cable length is longer than your pipe length, spiral the cable evenly along the length of pipe.

• 

NAMSRK has a 5W/lin ft output. Ensure all metal pipes get 5W/lin ft. 

• 

For 2” pipes and each 2” in diameter, double the output.

• 

Por plastic pipes, consider 25% more heat required.

Code

Length in ft

Voltage

Power output on pipe at 40°F 

(5°C) in W

Power output on pipe at 50°F 

(10°C) in W

Power output in ice & snow at 32°F 

(0°C) in W

NAMSRK-6FT

6

110-120

36

30

60

NAMSRK-12FT

12

110-120

72

60

120

NAMSRK-18FT

18

110-120

108

90

180

NAMSRK-24FT

24

110-120

144

120

240

NAMSRK-50FT

50

110-120

300

250

500

NAMSRK-75FT

75

110-120

450

375

750

NAMSRK-100FT

100

110-120

600

500

1000

SPECIFICATIONS

Service voltage

110-120V

Normal cable width (in/mm)

0.42 (10.6)

Normal cable thickness (in/mm)

0.23 (5.8)

Cable bus wire gauge (AWG)

16

Cold lead length (in/mm)

30 (762)

Min. Circuit breaker size (Amps)

15

Max. Exposure Temperature

185

°F 

(85

°C

)

Electrical classification

Nonhazardous

Nominal Power Output Chart